ETX-1640x Power Requirements
- Updated2025-10-31
- 2 minute(s) read
ETX-1640x Power Requirements
Provide AC power connection to facility power source and connection to protective earth ground.
The power entry panel (PEP) used in your system depends on your High-Power Production Test Base System model. Refer to ETX-1640x System PEP Ratings for more information about the PEP ratings for your specific model.
| Specification | RMX-10140-50D4P (ETX-16400) | RMX-10140-50Y2P (ETX-16401) |
|---|---|---|
| Overall power consumption | 40 kW | 30 kW |
| Overvoltage category | II | II |
| Branch circuit rating | 63 A | 63 A |
| Voltage rating | 480 V 3P+PE, 3Φ | 100 V/173 V to 240 V/415 V, 3P+N+PE, 3Φ |
| Frequency | 50 Hz or 60 Hz | 50 Hz or 60 Hz |
| Current rating | 50 A | 50 A |
| Component | RMX-10140-50D4P (ETX-16400) | RMX-10140-50Y2P (ETX-16401) |
|---|---|---|
| Hardwired input protective enclosure screws |
Tool: 3 mm hex driver Torque: 1.3 N m (11.5 lb · in.) |
Tool: 3 mm hex driver Torque: 1.3 N m (11.5 lb · in.) |
| Earth termination mechanical lug |
Tool: 3/16 hex driver Torque: 5.1 N · m (45 lb · in.) Wire gauge: 14 AWG to 2/0 AWG Wire strip length: 15.7 mm (0.6 in.) |
Tool: 3/16 hex driver Torque: 5.1 N · m (45 lb · in.) Wire gauge: 14 AWG to 2/0 AWG Wire strip length: 15.7 mm (0.6 in.) |
| M6 screw thread input terminal block |
Tool: #2 Phillips driver Torque: 2.5 N m to 3.0 N m (22.1 in. lb. to 26.6 in lb.) Wire gauge: 14 AWG to 2 AWG Wire strip length: 14.0 mm (0.6 in.) |
Tool: #2 Phillips driver Torque: 2.5 N m to 3.0 N m (22.1 in. lb. to 26.6 in lb.) Wire gauge: 14 AWG to 2 AWG Wire strip length: 14.0 mm (0.6 in.) |
| Insulator termination for neutral |
Tool: 4 mm hex driver Torque: 2.8 N m (25 lb · in.) |
N/A |
| Cable grommet |
Part number: Heyco M4860 Cable bundle diameter: 22.0 mm to 32.0 mm (0.9 in. to 1.2 in.) |
Part number: Heyco M4860 Cable bundle diameter: 22.0 mm to 32.0 mm (0.9 in. to 1.2 in.) |
For the input power cable, NI recommends copper wire at least 10 mm2 (8 AWG) minimum. Installation of the ETX-1640x to the facilities must be made per the local electrical code requirement, and a qualified electrical contractor should make the installation.
Related Information
- Fuse Ratings for Power Components
Refer to the following sections for detailed information on the fuse ratings for the power entry panels (PEP) in the ETX-16400/16401 and the secondary 480 V transformer in the ETX-16400.
- ETX-1640x System PEP Ratings
The power entry panel (PEP) used in your system depends on your High-Power Production Test Base System model.