Use the NI-SLSC API to configure SET-1240 channel modes and configure xVDT channels as 6-wire or 4/5-wire mode.

Common Properties for Configuration

Use the following common NI-SLSC properties to program the SET-1240.

Table 10. Module Characteristic Properties
Property Name Data Type Property Type Description
SET.Module.CurrTemp Double Device Returns the current temperature of the module in degrees Celsius. Read-only.
Table 11. Configuration Mode Properties
Property Name Data Type Property Type Description Valid Values
SET.xVDt.mode I32 enum Physical Channel: xVDT_Chx, where x is the channel number.

Sets the configuration mode for the xVDT channel.

0 = disable

30 = operational

33 = testMode

SET.xVDt.wiring U32 Physical Channel: xVDT_Chx, where x is the channel number.

Sets the wiring mode for the xVDT channel.

0 = 6-wire

1 = 4-wire/5-wire

Table 12. Self Test Properties
Property Name Data Type Property Type Description Valid Values
SET.Test.x_enable U32 Physical Channel: selftestConfiguration

Enables internal +10 V for Test_CNTL gain control.

0 = disable

1 = enable

SET.Test.exc_source U32 Physical Channel: selftestConfiguration

Connect Test_Exc to Inst 0± for Test Excitation source.

0 = disconnect

1 = Inst 0±

SET.Test.CtrlV_transducer U32 Physical Channel: selftestConfiguration

Select Test_A+ or Test_B+ to connect to Test_Output.

0 = Test_A+

1 = Test_B+

SET.Test.CtrlV_measureline U32 Physical Channel: selftestConfiguration

Connect Test_Output to Inst 1±.

0 = disconnect

1 = Inst 1±