Configuring the Device
- Updated2026-05-04
- 1 minute(s) read
Use the NI-SLSC API to configure SET-1240 channel modes and configure xVDT channels as 6-wire or 4/5-wire mode.
Common Properties for Configuration
Use the following common NI-SLSC properties to program the SET-1240.
| Property Name | Data Type | Property Type | Description |
|---|---|---|---|
| SET.Module.CurrTemp | Double | Device | Returns the current temperature of the module in degrees Celsius. Read-only. |
| Property Name | Data Type | Property Type | Description | Valid Values |
|---|---|---|---|---|
| SET.xVDt.mode | I32 enum | Physical Channel: xVDT_Chx, where x is the channel number. |
Sets the configuration mode for the xVDT channel. |
0 = disable 30 = operational 33 = testMode |
| SET.xVDt.wiring | U32 | Physical Channel: xVDT_Chx, where x is the channel number. |
Sets the wiring mode for the xVDT channel. |
0 = 6-wire 1 = 4-wire/5-wire |
| Property Name | Data Type | Property Type | Description | Valid Values |
|---|---|---|---|---|
| SET.Test.x_enable | U32 | Physical Channel: selftestConfiguration |
Enables internal +10 V for Test_CNTL gain control. |
0 = disable 1 = enable |
| SET.Test.exc_source | U32 | Physical Channel: selftestConfiguration |
Connect Test_Exc to Inst 0± for Test Excitation source. |
0 = disconnect 1 = Inst 0± |
| SET.Test.CtrlV_transducer | U32 | Physical Channel: selftestConfiguration |
Select Test_A+ or Test_B+ to connect to Test_Output. |
0 = Test_A+ 1 = Test_B+ |
| SET.Test.CtrlV_measureline | U32 | Physical Channel: selftestConfiguration |
Connect Test_Output to Inst 1±. |
0 = disconnect 1 = Inst 1± |