Counter Input:General Properties:More:Advanced:Maximum Measurable Period Property
- Updated2023-02-21
- 1 minute(s) read
Short Name: CI.MaxMeasPeriod
Property of DAQmx Channel
Specifies the maximum period (in seconds) in which the device will recognize signals. For frequency measurements, a signal with a higher period than the one set in this property will return 0 Hz. For duty cycle, the device will return 0 or 1 depending on the state of the line during the max defined period of time. Period measurements will return NaN. Pulse width measurement will return zero.
Remarks
The following table lists the characteristics of this property.
Permissions | read/write |
Resettable | yes |
Settable while task is running | device-specific |
Available in Run-Time Engine | yes |