NI-9211 Vendor Configuration Extensions
- Updated2024-09-13
- 1 minute(s) read
NI-9211 Vendor Configuration Extensions
The following table lists the vendor configuration extensions for the NI-9211.
Index | Sub | Type | R/W | Description |
---|---|---|---|---|
0x2001 | 0 | ARR:U32 | — | Scan List = 7 |
1 | R | Channels to Convert = <1..6>, default = 6 | ||
2..7 | R/W | Channel Number |
NI-9211 Scan List
The scan list is a simple, ordered list of channels to convert. The NI-9211 has a total of six measurable channels.
- <0..3>: four input channels (always measured in a ±80 mV range)
- 4: one cold junction channel (always measured in a ±2.5 V range)
- 5: one auto zero channel (always measured in a ±80 mV range)
Index | Sub | Type | Value |
---|---|---|---|
0x2001 | 0 | ARR:U32 | 7 |
1 | 6 | ||
2 | 0 | ||
3 | 1 | ||
... | ... | ||
7 | 5 |
NI-9211 Calibration Data
Calibration data is set by the device driver during initialization and the calibration conversion is performed on the module ADC.