Flicker VIs
- Updated2025-12-23
- 1 minute(s) read
Owning Palette: Power Quality VIs
Requires: Electrical Power Toolkit. This topic might not match its corresponding palette in LabVIEW depending on your operating system, licensed product(s), and target.
Use the Flicker VIs to measure instantaneous flicker sensation, short-term flicker severity, and long-term flicker severity as defined in IEC 61000-4-15:2010.
| Palette Object | Description |
|---|---|
| Instantaneous Flicker Sensation | Calculates the instantaneous flicker values of a voltage waveform, according to IEC 61000-4-15:2010. This VI supports measuring single-bus single-line or multiple-bus single-line systems. |
| Long-Term Flicker Severity | Aggregates short-term flicker values and returns the long-term flicker of a voltage waveform, according to IEC 61000-4-15:2010. Long-term flicker is the cubic average of short-term flicker values recorded over a two-hour period. This VI supports measuring single-bus single-line or multiple-bus single-line systems. |
| Short-Term Flicker Severity | Aggregates instantaneous flicker values and returns the short-term flicker of a voltage waveform for a 10-minute period, according to IEC 61000-4-15:2010. This VI supports measuring single-bus single-line or multiple-bus single-line systems. |