Some drivers have unique object parameters. Here is a list:
UpdateOutputs specifies how many poll requests pass before the driver rewrites all outputs to the device. For example, if UpdateOuptuts equals 10, then every tenth time the Modbus object receives a poll request, it writes all output values to the device. This ensures that the device is synchronized with Lookout. The default value is 100.
RefreshOutputs specifies whether or not the driver regularly rewrites all outputs every UpdateOuptuts poll requests. If RefreshOuptuts is equal to 1 (the default value), the driver output rewrite function is turned on. If RefreshOuptuts is equal to 0 (zero), the driver output rewrite function is turned off; no rewriting of output values occurs except when they change.
Note: Most driver objects always write all outputs whenever they first start, and whenever they recover from a communication failure.
DiagnosticFile or DiagnosticPath specifies a filename (including full path) or just the path to a file for a logfile of a non-serial port communication (for example, Ethernet) between Lookout and the device for troubleshooting. For example, DiagnosticPath=c:\temp\diag.txt. Refer to the table below for more details about each object.
Obejectname (.cbx) | Filename (.ini) | Sectionname | Keyname [=default value] | Description |
allbrad.cbx | allbrad.ini | [PLC2] | UnprotectedWrite= | To disable an STS error reported by the Allen Bradley PLC when trying to write to protected registers on the PLC. It allows writing to protected registers. For example: [PLC2] Unprotected Write=yes |
allbrad.ini | [KT] | TranslateLogical Address= | Converts logical address to physical (See DF1 protocol specification; Chapter: PLC-2 physical Addressing). For example: [KT] TranslateLogical Address=yes | |
daniel.cbx | daniel.ini | [all]/[objname] | UpdateOutputs=100 | Sets the amount of polls to skip an output update. |
daniel.ini | [all]/[objname] | RefreshOutputs=1 | Sets to refresh all outputs every UpdateOutput polls. | |
daniel.ini | [all]/[objname] | SkipImmediatePoll=0 | Sets to poll immediately upon getting a connection. | |
daniel.ini | [all]/[objname] | ConfirmPoll=0 | Sets to poll immediately to confirm writes. | |
daniel.ini | [all]/[objname] | SkipPollBefore Write=0 | Sets to skip a read poll before write (could be TRUE, in case of ConfirmPoll TRUE). | |
daniel.ini | [All] | MaxChannels=8 | Sets max number of paths that can be open. | |
devnet.cbx | devnet.ini | [all] | StartupDelay=10 | Number of seconds to delay before first poll to device; default is 10 secs. For example: [all] StartupDelay=20 |
fpoint.cbx | fpoint.ini | [objname] | FilterChAlarms=0 | Filters several alarms coming from the FieldPoint driver: FP module - channel status - Error message FP-AI-1xx - 1 - Out of range FP-AO-200 - 1 - Open Current Loop FP-AO-210 - 1 - Overcurrent Protection FP-DO-410 - 1 - Current Limited FP-TC-120 - 1 - Out of Range FP-RTD-122 - 1 - Out of Range FP-CTR-500 - 1 - Overflow since Last Read For example: [FieldPoint1] FilterChAlarms=1 |
ge.cbx | ge.ini | [ge]/[objname] | OkToWriteUnchanged Values=0 | Specifies to perform block writes. For example: [GE1] OkToWrite Unchanged Values=1 |
hitachie.cbx1 | hitachie.ini | [ethernet] | DiagnosticPath= | Creates a diagnostic file for Ethernet communication. For example: [ethernet] DiagnosticPath= c:\temp\ hitachiediag.txt |
modbus.cbx | modbus.ini | [ethernet] | DiagnosticPath= | Creates a diagnostic file for Ethernet communication. For example: [ethernet] DiagnosticPath= c:\temp\ modbusdiag.txt |
modbus.ini | [all]/[objname] | UpdateOutputs=100 | Sets the amount of polls to skip an output update. | |
modbus.ini | [all]/[objname] | RefreshOutputs=1 | Sets to refresh all outputs every UpdateOutput polls. | |
modbus.ini | [all]/[objname] | SkipImmediatePoll=0 | Sets to poll immediately upon getting a connection. | |
modbus.ini | [all]/[objname] | AlwaysWrite=0 | Sets to always write redundant writes. | |
modbus.ini | [all]/[objname] | OptimizeWrite=0 | Sets to write Coils/Register optimized. | |
modbus.ini | [all]/[objname] | Protocol=RTU | Sets protocol mode; RTU or ASCII. For example: [Modbus1] Protocol=ASCII | |
modbus.ini | [All] | MaxChannels=8 | Sets max number of paths that can be open. | |
mtsbshi.cbx | mtsbshi.ini | [all]/[objname] | UpdateOutputs=100 | Sets the amount of polls to skip an output update. |
mtsbshi.ini | [all]/[objname] | RefreshOutputs=1 | Sets to refresh all outputs every UpdateOutput polls. | |
nif.cbx2 | lookout.ini | [Fieldbus] | AlarmPriority=0 | Alarm priority for Fieldbus objects. (default = 0) |
optohost.cbx | optohost.ini | [Diagnostics] | TransactionFile= | Creates a diagnostic file for Ethernet communication. |
optomist.cbx | optomist.ini | [all]/[objname] | UpdateWrites=0 | Sets to refresh all outputs every 100 polls. |
s5as511.cbx2 | lookout.ini | [S5-AS511] | Diagnostics=0 | Turns on diagnostic recording functions in S5-AS511 driver. When activated, this option logs diagnostic information to the s5as511.dai file in the Lookout directory. =0 diagnostics are off (default) =1 diagnostics are on |
s7_hmi.cbx2 | s7_hmi.ini | [COMx] x=1.. | MPIBaud=Auto | Specifies the speed at which the MPI Network is operating. These selections are possible. "187.5K", "Auto". For example: [COM2] MPIBaud=Auto HighestMPI=68 PanelMPI=34 |
s7_hmi.ini | [COMx] x=1.. | HighestMPI=31 | The highest possible MPI address for any device on the network. The range for this setting is from 0 to 126; the default is 31. | |
s7_hmi.ini | [COMx] x=1.. | PanelMPI= | The MPI address assigned to the hardware adapter that is being used to talk to the network. The range for this setting is from 0 to the HighestMPI setting. | |
siemens.cbx | siemens.ini | [objname] | InitTimeout=2 | Sets the time that the application association will lock out other block's calls to funcs like tf_receive and tf_send; 1..10 seconds. For example: [PLC1] InitTimeout=3 |
sixnet.cbx2 | lookout.ini | [Sixnet] | IOMAPAlarm Priority=5 | Priority of the "Unable to load Sixnet IOMAP library: iobase32.dll" alarm in Sixnet. (default = 5) |
lookout.ini | ProjectAlarm Priority=5 | Priority of the "No Sixnet configuration currently loaded" alarm in Sixnet. (default = 5) | ||
squared.cbx | squared.ini | [all] | Bit1Addressing | Sets bit addressing to 1-16 instead of 0-15. For example: [SquareD1] Bit1Addressing=1 |
squared.ini | [ethernet] | DiagnosticFile= | Creates a diagnostic file for Ethernet communication. For example: [SquareD1] DiagnosticFile= c:\temp\ squareddiag.txt | |
tesco.cbx | tesco.ini | [Diagnostics] | DiagnosticFile= | Creates a diagnostic file for Tesco communication. |
tesco.ini | [Diagnostics] | Setpoint=0 | Turns on Setpoint logs for DiagnosticFile. | |
tesco.ini | [Diagnostics] | GeneralComm=0 | Turns on GeneralComm logs for DiagnosticFile. | |
tesco.ini | [All]/[objname] | SPDeviation=0 | A deviation for setpoint writes. | |
tiway.cbx | lookout.ini | [Tiway] | DiagnosticFile= | Creates a diagnostic file for Tiway communication. For example: [Tiway] DiagnosticFile= c:\temp\ tiwaydiag.txt |
lookout.ini2 | [Tiway]/[objname] | UpdateOutputs=100 | Sets to refresh all outputs every UpdateOutputs polls (=0 disables to refresh all outputs). | |
lookout.ini | [objname] | ConfirmPoll=0 | Sets to do a confirm poll, in addition it will skip doing the poll before the write. | |
tiway.ini | [PCAcardx] x=1..4 | BaseAddress= | Sets base address for the cards can be set anywhere from 0x8000 to 0xFF00 (DOS area: 0xA000..0xEF00) NOTE: BaseAddress and Irq are not required to be set in .ini because the driver searches automatically for it. However, if you set it in the .ini, the object uses those settings. It assumes that PCAcard1 has the lowest base address and so on. | |
tiway.ini | [PCAcardx] x=1..4 | Irq= | Sets IRQ for the PC Adapter cards and can be anywhere from 1..15 (0=No IRQ). NOTE: BaseAddress and Irq are not required to be set in .ini because the driver searches automatically for it. However, if you set it in the .ini, the object uses those settings. | |
tiway.ini3 | [SFx] x=1.. | macro-string | Configure Store and forward macros into Tiway structure (See SIEMENS TIWAY Host Adapter Card Manual). For example: [SF1] <C/V> <source-offset> <count> <msec> <dest-block> <dest-offset> | |
tiway.ini3 | [UHA1COMx] x=1.. [PCAcardx] x=1.. | Optionxx=0xFFFF | Read Host Adapter command 30 (configure network manager) optional settings. Network manager configuration options ( 00 - 0E (00 unused)): xx=01..0E (See SIEMENS TIWAY Host Adapter Card Manual) | |
vmax.cbx | vmax.ini | [ethernet] | DiagnosticPath= | Creates a diagnostic file for Ethernet communication. For example: [ethernet] DiagnosticPath= c:\temp\ vmaxdiag.txt |
Object name (.cbx) | File name (.ini) | Section name | Keyname [=default value] | Description |
animator.cbx | lookout .ini | [Custom Colors] | 0= … 15= … | Stores up to 16 custom colors for the Animator object. For example: [Custom Colors] 0=0x0000FF |
hyper.cbx | lookout .ini | [System] | SkipTrend Warning=0 | Skips the warning dialog of the HyperTrend object when you add traces to it that the trace has to be enabled for logging. |
hyper .ini | [HyperTrend] | MaxScrollRate =330 | Sets the max scroll rate from the .ini file (in milliseconds per pixel). Default is 0.33 s per ScrollPixels. | |
hyper .ini | [HyperTrend] | ScrollPixels=8 | Sets the max number of pixels to scroll at a time (this affects the scroll rate also). | |
hyper .ini | [objname] | ForceAsynch=0 | Sets to force the synchronous traces (discretes) to be drawn asynchronously (interpolated). | |
pager.cbx | pager .ini | [objname] | DisableLog OffAck Check=0 | 1: Sets to disable verification of the log off ack. |
pot.cbx2 | lookout .ini | [Pots]/[objname] | SnapDelay=2 | Sets snap delay setting for Pots (1..4200000 seconds). |
lookout .ini | [Pots] | Mouse ButtonRepeat=1 | 1: User holds down the mouse button and the incr, decr buttons will make the Pot change values several times. 0: Can be used to disable this default behavior. | |
recipe.cbx2 | lookout .ini | [Recipe] | objname. alarmpriority=8 | Alarm priority used by a Recipe object (default = 8). For example: [Recipe] Recipe1. alarmpriority=4 |
sheet.cbx2 | lookout .ini | [DataPath] | objname= | Full path name for an individual spreadsheet (default is path to the Lookout data directory). |
table.cbx2 | lookout .ini | [LocalTable] /[objname] | Delay=500 | Periodically post a DDE table with this frequency (measured in ms). (default = 500) |
lookout .ini | [LocalTable] /[objname] | EchoCursor =1 | 0: only echo a cursor value if the cell the cursor is pointing to does not have a connection to it. 1: no echoes (default) | |
lookout .ini | [LocalTable] /[objname] | PokeAllCells =0 | Sets to poke all cells. This setting exists to work around a possible bug in DDE. If in CF_TEXT mode (must be to work with Excel), you need to be sending the whole table in each DDE message. But Lookout does not, so this function pokes every cell instead of just the one that changed. PokeAllCells gets called instead of PokeCell if you have the .ini setting PokeAllCells=1. | |
for all old 3.8 .cbx | lookout .ini | [System] | ShowObsolete =1 | Shows obsolete .cbx file in the Object Explorer (for example, nidaq.cbx and other 3.8 objects). Note: NI recommends that you no longer use the old Lookout 3.8 objects. |
1 Lookout 5.1 or later is required for this setting.
2 You can find more information about this option in the Lookout Help.
3 Potentially not supported by third-party devices.