Grounding the cRIO-9803
- Updated2023-02-06
- 1 minute(s) read
Grounding the cRIO-9803
You must connect the cRIO-9803 grounding terminal to the grounding electrode system of the facility.
Note For more information about ground
connections, visit ni.com/r/emcground.
What to Use
- Right angle ring lug
- Wire, 1.3 mm2 (16 AWG) or larger
- Screwdriver, Phillips #2
What to Do
Complete the following steps to ground the cRIO-9803.
-
Attach the ring lug to the wire.
Note NI recommends using a right angle ring lug to ensure sufficient cabling clearance for the ground wire. If your system uses a single module, a standard ring lug may be sufficient for cabling clearance.
- Remove the grounding screw from the grounding terminal on the bottom of the module.
- Fasten the ring lug to the grounding terminal.
- Tighten the grounding screw to 0.5 N · m (4.4 lb · in.) of torque.
- Attach the other end of the wire to the chassis safety ground using a method that is appropriate for your application.