Mounting the cRIO-904x
- Updated2025-05-05
- 2 minute(s) read
To obtain the maximum ambient temperature, you must mount the cRIO-904x in the reference mounting configuration shown in the following image. Mounting the cRIO-904x in the reference mounting configuration ensures that your system will operate correctly across the full operating temperature range and provide optimal C Series module accuracy.
Observe the following guidelines to mount the cRIO-904x in the reference mounting configuration.
- Horizontal mounting orientation.
- Mounting substrate options:
- Mount the cRIO-904x directly to a metallic surface that is at least 1.6 mm (0.062 in.) thick and extends a minimum of 101.6 mm (4 in.) beyond all edges of the device.
- Use the NI Panel Mounting Kit to mount the cRIO-904x to a metallic surface that is at least 1.6 mm (0.062 in.) thick and extends a minimum of 101.6 mm (4 in.) beyond all edges of the device.
- Observe the cooling dimensions in Mounting Requirements for the cRIO-904x.
- Allow space for cabling clearance according to Mounting Requirements for the cRIO-904x.
Tip Before using any of these mounting methods, record the serial number from the back of the cRIO-904x so that you can identify the cRIO-904x in MAX. You will be unable to read the serial number after you mount the cRIO-904x.
Related Information
- Mounting Requirements for the cRIO-904x
Use the following to ensure you meet the cooling and cabling clearance requirements for mounting cRIO-904x models.