Connecting the cRIO-903x to Power
- Updated2022-11-08
- 3 minute(s) read
Connecting the cRIO-903x to Power
The cRIO-903x requires a 9 V to 30 V external power supply. The cRIO-903x filters and regulates the supplied power and provides power for the C Series modules. The cRIO-903x has a primary power input, V1, and a secondary power input, V2.
The POWER LED on the cRIO-903x indicates which power input is in use. Refer to POWER LED Indicators for more information about the POWER LED states.
Notice Do not connect V2 to a DC
mains supply or to any supply that requires a connecting cable longer than 3 m
(10 ft). A DC mains supply is a local DC electricity supply
network in the infrastructure of a site or building.
What to Use
- Ferrite (781233-02), included with the cRIO-903x
- Screwdriver, 2.54 mm (0.10 in.) flathead
- Primary power supply:
- (cRIO-9030/9031/9032/9033/9034) 9 V to 30 V, 40 W minimum
- (cRIO-9035/9036/9037/9038/9039) 9 V to 30 V, 46 W minimum
- (Optional) Secondary power supply:
- (cRIO-9030/9031/9032/9033/9034) 9 V to 30 V, 40 W minimum
- (cRIO-9035/9036/9037/9038/9039) 9 V to 30 V, 46 W minimum
NI recommends the power supplies listed in the following table for the cRIO-903x.
| Power Supply | Part Number |
|---|---|
| NI PS-15 Industrial Power Supply (24 V DC, 5 A, 100 V AC to 120 V AC/200 V AC to 240 V AC input) | 781093-01 |
| NI PS-10 Desktop Power Supply (24 V DC, 5 A, 100 V AC to 120 V AC/200 V AC to 240 V AC input) | 782698-01 |
What to Do
Complete the following steps to connect a power supply to the cRIO-903x.
- Ensure that your power supply is powered off.
-
Install the ferrite on the negative and positive leads of the power supply, as shown in the following figure.
Figure 14. Installing a Ferrite on the Power Leads
- Pass the leads through the ferrite twice, leaving 50 mm to 75 mm (2 in. to 3 in.) between the ferrite and the end of the leads.
- Close the ferrite around the leads.
-
Remove the power connector from the cRIO-903x.
Caution Do not tighten or loosen the terminal screws on the power connector while the cRIO-903x is powered on.Attention Ne pas serrer ou desserrer les vis des bornes sur le connecteur d'alimentation pendant que le cRIO-903x est sous tension.
-
Connect the primary power supply and optional secondary power supply to the power connector, as shown in the following figure.
Figure 15. Power Connections
Note The C terminals are internally connected to each other. - Tighten the terminal screws on the power connector to 0.20 N · m to 0.25 N · m (1.8 lb · in. to 2.2 lb · in.) of torque.
- Install the power connector on the front panel of the cRIO-903x.
- Tighten the power connector screw flanges to 0.20 N · m to 0.25 N · m (1.8 lb · in. to 2.2 lb · in.) of torque.
- Power on the primary power supply and optional secondary power supply.