The following items are known issues in NI-TimeSync 15.0 sorted by Date.
ID | Known Issue | |||||
---|---|---|---|---|---|---|
246727 Return |
Changing the priority in NI MAX or the Web-based Configuration & Monitoring Utility may leave ni-rt.ini in an inconsistent state. Workaround: N/A
|
|||||
477434 Return |
The NI-TimeSync Software-Based 1588 plug-in fails to synchronize properly when used with a secondary network adapter on PharLap ETS and VxWorks targets. Workaround: National Instruments recommends that you only use the primary network adapter when using the NI-TimeSync Software-Based 1588 plug-in.
|
|||||
493251 Return |
Running an ARM-based Linux Real-Time target as a 1588 master may degrade synchronization. Workaround: National Instruments recommends that you only use ARM-based targets running NI Linux Real-Time as 1588 slaves. ARM-based targets running NI Linux Real-Time are slave only by default.
|
Document last updated on 8/3/2015