TB-12395 Specifications

TB-12395 Specifications

The following specifications are typical at 25 °C unless otherwise noted.

TB-12395 Pinout

Use the pinout to connect to terminals on the TB-12395.



Note K indicates pins removed for connector keying.
Note Unmapped pins to the screw terminals are left unconnected.

Physical Connectors

The following figure shows the connections on the TB-12395 board assembly.

Figure 1. TB-12395 Top View


  1. Mounting screw
  2. Enclosure base
  3. Metal bracket
  4. 48-pin DIN 41612 connector
  5. Ground lug
  6. I/O channel name
  7. 16-pos screw terminal
  8. DIN 41612 pin name
Note Terminal J4 can be used for Chassis Ground, which is tied to the metal case standoffs, metal bracket, jack-sockets, and the enclosure base.
Note The I/O channels are routed in differential pairs. For example, 0 is paired with COM 0. Each screw terminal consists of 8 I/O channels grouped into one port, while J2 is assigned as Port 0 or Port 2, and while J3 is assigned as Port 1 or Port 3 .
Note DIN 41612 connector and screw terminals are isolated from Chassis Ground.

Panel Mounting the TB-12395 Terminal Block

The terminal block comes pre-equipped with a removable DIN rail clip for mounting to a standard DIN rail.

Figure 2. Terminal Block with DIN Rail Clip


The terminal block can also be rear panel mounted using the pattern provided below for M4 × 0.7 threaded holes.

Figure 3. Terminal Block Rear Hole Pattern


Caution If you are using the TB-12395 with voltage greater than 30 Vrms, 42.4 Vpk, 60 Vdc, the terminal block must be mounted in a closed rack to prevent user access to the rear end of the device.

Physical Characteristics

Dimensions

105.6 mm x 59.4 mm x 137.4mm (4.16 in. x 2.34 in. x 5.41 in.)

Weight

280 g (9.9 oz)

Connectors

1x male 48-pin DIN 41612 Connector, 2x 16-pos Sauro MSBH16045-0N Screw Terminals

Screw-terminal wiring

16 AWG to 30 AWG copper conductor wire with minimum temperature rating of 80 °C and minimum voltage rating of 100 V

Torque for screw terminals

0.5 N·m to 0.6 N·m (4.42 lb·in to 5.31 lb·in)

Safety Voltages

Connect only voltages that are below these limits.

Maximum input voltage

100 V peak

Isolation

Channel-to-channel

None

Channel-to-earth

Continuous working voltage

100 V peak

Transient overvoltage[1]1 The short duration overvoltage of a few milliseconds or less, oscillatory or non-oscillatory, usually highly damped.

920 V peak

Caution If you are using the TB-12395 with voltages greater than 30 V RMS, 42.4 V peak, or 60 V DC, the SLSC chassis must be panel mounted in a closed rack to prevent user access to the rear of the device.
Attention Si vous utilisez le TB-12395 avec des tensions supérieures à 30 V RMS, 42.4 V peak, ou 60 V DC, le châssis SLSC doit être sécurisé contre les contacts. Pour cela, il est nécessaire de le monter sur panneau dans un rack fermé pour empêcher l'utilisateur d'accéder à l'arrière de l'appareil.

These test and measurement circuits are rated for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS.

MAINS is a hazardous live electrical supply system to which equipment is designed to be connected to for the purpose of powering equipment. This product is rated for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics.

Safety Compliance Standards

This product is designed to meet the requirements of the following electrical equipment safety standards for measurement, control, and laboratory use:

  • IEC 61010-1, EN 61010-1
  • Conforms to UL Standard 61010-1 and UL Standard 61010-2-030
  • Certified to CSA Standard C22.2 # 61010-1 and CSA Standard C22.2 # 61010-2-030


Note For safety certifications, refer to the product label or the Product Certifications and Declarations section.

Electromagnetic Compatibility Standards

This product meets the requirements of the following EMC standards for electrical equipment for measurement, control, and laboratory use:

  • EN 61326-1 (IEC 61326-1): Class A emissions; Basic immunity
  • EN 55011 (CISPR 11): Group 1, Class A emissions
  • AS/NZS CISPR 11: Group 1, Class A emissions
Note Group 1 equipment (per CISPR 11) is any industrial, scientific, or medical equipment that does not intentionally generate radio frequency energy for the treatment of material or inspection/analysis purposes.

CE Compliance

This product meets the essential requirements of applicable European Directives, as follows:

  • 2014/30/EU; Electromagnetic Compatibility Directive (EMC)
  • 2011/863/EU; Restriction of Hazardous Substances (RoHS)
  • 2014/35/EU; Low-Voltage Directive (Safety)

Product Certifications and Declarations

Refer to the product Declaration of Conformity (DoC) for additional regulatory compliance information. To obtain product certifications and the DoC for NI products, visit ni.com/product-certifications, search by model number, and click the appropriate link.

NI Services

Visit ni.com/support to find support resources including documentation, downloads, and troubleshooting and application development self-help such as tutorials and examples.

Visit ni.com/services to learn about NI service offerings such as calibration options, repair, and replacement.

Visit ni.com/register to register your NI product. Product registration facilitates technical support and ensures that you receive important information updates from NI.

NI corporate headquarters is located at 11500 N Mopac Expwy, Austin, TX, 78759-3504, USA.

1 The short duration overvoltage of a few milliseconds or less, oscillatory or non-oscillatory, usually highly damped.