NI-9485 Specifications
- Updated2024-11-25
- 5 minute(s) read
Definitions
Warranted specifications describe the performance of a model under stated operating conditions and are covered by the model warranty.
Characteristics describe values that are relevant to the use of the model under stated operating conditions but are not covered by the model warranty.
- Typical specifications describe the performance met by a majority of models.
- Nominal specifications describe an attribute that is based on design, conformance testing, or supplemental testing.
Specifications are Typical unless otherwise noted.
Conditions
Specifications are valid for the range -40 °C to 70 °C unless otherwise noted.
NI-9485 Pinout
Signal | Description |
---|---|
CHa and CHb | Interchangeable signal connections |
Output Characteristics
Number of channels | 8 digital output channels | ||||||
Relay type | Normally open solid-state relay (SSR) | ||||||
Switching voltage | 60 V DC maximum, 30 V rms maximum | ||||||
| |||||||
Switching rate (90% duty cycle)[1] | 1 operation per second | ||||||
Relay open time | 0.5 ms, typical | ||||||
Relay close time | 9.0 ms, typical | ||||||
On resistance | 200 mΩ maximum | ||||||
Off stage leakage | 30 μA, typical | ||||||
MTBF | 2,172,740 hours at 25 °C; Bellcore Issue 6, Method 1, Case 3, Limited Part Stress Method |
Safety Voltages
Connect only voltages that are within the following limits.
Maximum Voltage, Channel a to Channel b | 60 V DC, 30 V RMS | ||||||||||||||||||||||||||
|
Measurement Category I
Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics.
Measurement Category II
Measurement Category II is for measurements performed on circuits directly connected to the electrical distribution system. This category refers to local-level electrical distribution, such as that provided by a standard wall outlet, for example, 115 V for U.S. or 230 V for Europe.
Environmental Characteristics
| |||||||||||||
| |||||||||||||
Ingress protection | IP40 | ||||||||||||
Pollution Degree | 2 | ||||||||||||
Maximum altitude | 5000 m | ||||||||||||
|
To meet these shock and vibration specifications, you must panel mount the system.
Power Requirements
| |||||||
|
Physical Characteristics
| |||||||||||||||
| |||||||||||||||
Weight | 145 g (5.1 oz) |
1 For additional specifications related to faster switching rates and/or higher currents at lower temperatures, go to ni.com/info and enter the info code rd9485specs.