Chien-Hrones-Reswick Autotuning Method
- Updated2023-02-21
- 4 minute(s) read
The Chien-Hrones-Reswick autotuning method focuses on setpoint response and disturbance response. This method provides formulas for 0% and 20% overshoot.
![]() |
Note You must use the PID Autotuning Design VI to implement this autotuning method. Select the Chien-Hrones-Reswick polymorphic instance and use the Tuning specifications input to configure which formula you want to use. |
The following tables shows the Chien-Hrones-Reswick recommendations for each tuning formula:
| Regulator – 0% overshoot | |||
|---|---|---|---|
| Controller | Kc | Ti | Td |
| P | 0.3TP/![]() |
— | — |
| PI | 0.6TP/![]() |
4![]() |
— |
| PID | 0.95TP/![]() |
2.4![]() |
0.42![]() |
where TP is the time constant and
is the deadtime.
| Regulator – 20% overshoot | |||
|---|---|---|---|
| Controller | Kc | Ti | Td |
| P | 0.7TP/![]() |
— | — |
| PI | 0.7TP/![]() |
2.3![]() |
— |
| PID | 1.2TP/![]() |
2![]() |
0.42![]() |
where TP is the time constant and
is the deadtime.
| Servo – 0% overshoot | |||
|---|---|---|---|
| Controller | Kc | Ti | Td |
| P | 0.3TP/![]() |
— | — |
| PI | 0.35TP/![]() |
1.2![]() |
— |
| PID | 0.6TP/![]() |
![]() |
0.5![]() |
where TP is the time constant and
is the deadtime.
| Servo – 20% overshoot | |||
|---|---|---|---|
| Controller | Kc | Ti | Td |
| P | 0.7TP/![]() |
— | — |
| PI | 0.6TP/![]() |
![]() |
— |
| PID | 0.95TP/![]() |
1.4![]() |
0.47![]() |
where TP is the time constant and
is the deadtime.