ETX-16301/16309 Specifications
- Updated2025-10-31
- 14 minute(s) read
ETX-16301/16309 Specifications
These specifications apply to the ETX-16301/16309.
Revision History
| Version | Date Changed | Description |
|---|---|---|
| 379242A-01 | October 2025 | Initial release. |
Looking For Something Else?
For information not found in the specifications for your product, such as operating instructions, browse Related Information.
Definitions
Warranted Specifications describe the performance of a model under stated operating conditions and are covered by the model warranty. Specifications account for measurement uncertainties, temperature drift, and aging. Specifications are ensured by design or verified during production and calibration.
Characteristics describe values that are relevant to the use of the model under stated operating conditions but are not covered by the model warranty.
Values are Typical unless otherwise noted.
Conditions
Refer to ni.com/docs for detailed specifications on the specific instruments used within the ETX-16301/16309.
These specifications apply to all ETX-16301/16309 configuration options unless otherwise noted. Specifications are valid for the system and all included instruments under the following conditions unless otherwise noted.
- ETX Inverter Production Test System environmental characteristics are met
- Instrument-level conditions are met
Calibration Conditions
The performance of an externally calibrated instrument is defined in the instrument specifications. Additionally, specifications for externally calibrated instruments are only valid if the conditions defined in the instrument specifications are met.
ETX-1630x Mass Interconnect Pinouts
The ETX-1630x has a mass interconnect component with the following measurement category, isolation voltages, and pinouts.
Measurement Category
Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics.
Isolation Voltages
Isolation voltages only apply to hazardous voltage pins on the mass interconnect connectors referenced in the following table. Connectors not referenced in the following table have no isolation voltage ratings and are not intended to handle voltages above 30 V RMS, 60 V DC, or 42.4 V peak.
| Connector | Isolation Barrier | Maximum Working Voltage | Transient Overvoltage |
|---|---|---|---|
| J9 | Channel-to-ground/earth (Common Mode) | 1500 V DC | 0 V peak |
| J11 | Channel-to-ground/earth (Common Mode) | 230 V DC | 0 V peak |
| J12 | Channel-to-ground/earth (Common Mode) | 230 V DC | 0 V peak |
| J13 | Channel-to-ground/earth (Common Mode) | 300 V DC | 0 V peak |
| J15 | Channel-to-ground/earth (Common Mode) | 1500 V DC | 0 V peak |
J1 Pinout: Adapter Control and Communication
Refer to Additional Components for more information about the component type associated with J1.
J2 Pinout: DC PDU 1
J4 Pinout: DMM1, MATRIX1, and SMU1
Refer to Additional Components for more information about the component type associated with J4.
J6: RMX_PPS1
Refer to Additional Components for more information about the component type associated with J6.
J9: HP_PPS1
Refer to Additional Components for more information about the component type associated with J9.
J11 and J12: Pulser Current Output
Refer to Pulser Components for more information about the component type associated with J11 and J12.
J13: DMM2 and MUX1
Refer to Additional Components for more information about the component type associated with J13.
J15: Pulser and Power Signals DAQ Voltage
Refer to Pulser Components and Power Signals DAQ for more information about the component type associated with J15.
J17: SMIO1 and PXI_PPS1
Refer to Additional Components for more information about the component type associated with J17.
J18: Pulser and Power Signals DAQ Current
Refer to Pulser Components and Power Signals DAQ for more information about the component type associated with J18.
Input Voltage for the Power Entry Panel
The power entry panel (PEP) for the ETX-16301/16309 is the RMX-10140-50Y2P.
Input voltage range information is located in the ETX-1630x User Manual and ETX-1630x Specifications.
| Overvoltage category | II |
|---|---|
| Branch circuit rating | 63 A |
| Voltage rating |
ETX-16301: 100 V/173 V to 240 V/415 V, 3P+N+PE, 3Φ ETX-16309: 230 V/400 V, 3P+N+PE, 3Φ |
| Frequency | 50 Hz or 60 Hz |
| Current rating | 50 A |
Field Wiring Cable Specifications
The field wiring cable supplies power and protective earth for the ETX-1630x through internal terminal connections. Before performing initial power setup, you must provide a field wiring cable. The cable must meet the requirements in the following table.
| Outer diameter of the input power cable | 22.2 mm to 32 mm |
|---|---|
| Ground wiring | 2.5 mm2 to 70 mm2 (14 AWG to 2/0 AWG) |
| Wire strip length | 15.7 mm (0.6 in.) |
| Wiring for L1, L2, L3, and N[1]1 Neutral is applicable only for systems with the RMX-10140-50Y2P power entry panel. | 10 mm2 to 35 mm2 (8 AWG to 2 AWG) with M6 ring lugs installed |
| Minimum insulator temperature rating | 90 °C (194 °F) |
Receiver Ratings
The mass interconnect modules in the following table are capable of sourcing hazardous voltages.
| Module | Maximum Output Voltage |
|---|---|
| J9 | 1500 V DC |
| J11 | 230 V DC |
Hazardous voltages may be applied to the modules in the following table.
| Module | Maximum Input Voltage (Maximum Voltage Sink) |
|---|---|
| J11 | 230 V DC |
| J12 | 230 V DC |
| J13 | 300 V DC |
| J15 | 1500 V DC |
Pulser Specifications
Learn about specifications for the pulser and the RM-16061 high-voltage multiplexer device when used with the ETX-1630x.
The pulser generates a trapezoidal pulse.
- The pulser bias supply is an isolated supply that connects to outputs A0 (V+) and A1 (V-) on J11. Bias supply current and voltage are available only between these two pins.
- The pulse is a low voltage, ground referenced signal with a maximum potential of 20 V. If one of the bias outputs is in the pulse path, the bias supply becomes ground referenced during the pulse. It is critical that the pulser is the only connection to ground reference the DUT.
- The bias supply can power the DUT while taking measurements with the pulser. Do not pulse across the bias supply. Pulses are intended to be across other signal paths in the DUT. To protect the bias supply, the pulser does not allow pulses across A0 and A1. You can configure a pulse between A0 or A1 and another PULSER CURRENT OUTPUT on J11 or J12 while the bias supply is active.
| Maximum pulse current | 1200 A Maximum pulse current is the maximum supported value for the setpoint. |
|---|---|
| Maximum bias voltage | 230 V |
| Maximum bias current | 3 A |
| Maximum slew rate | 1 A/µs |
| Minimum rise time | 1 µs/A × Setpoint |
| Minimum fall time | 1 µs/A × Setpoint |
| Maximum pulse duration | 10 ms |
| Rating | 300 V, minimum |
|---|---|
| Minimum insulator temperature rating | 90 °C |
| Material | Copper |
| Size | 35 mm2 (2 AWG) |
Pulser Waveform Examples
Pulse Current Multiplexer Specifications
The RM-16061 high-voltage multiplexer device functions as a pulse current multiplexer in the ETX-1630x.
| Power | 24 V DC, 3 A |
|---|---|
| Charge | 20 V DC, 10 A |
| Bias | 230 V DC, 3 A |
| Pulse/load bus bar ratings | 20 V DC, 1200 A |
| Connector Name | Vendor | Part Number |
|---|---|---|
| Bias | Phoenix Contact | 1777808 |
| Charge | Weidmuller | 2459570000 |
| Power | Phoenix Contact | 1703350 |
| Ground screw | M4 × 0.7 |
|---|---|
| Maximum torque | 1.92 N · m (17.0 lb · in.) |
RM-16061 Fuse
The RM-16061 has a user serviceable time-delay fuse.
| Current rating | 12 A |
|---|---|
| Voltage rating | 20 V DC minimum |
| Size and dimensions | 5.2 mm × 20 mm |
| Type | Time-delay |
| Interrupt rating | 300 A |
| Recommended replacement | Eaton BK1-S505H(-V)-12-R |
ETX-1630x Physical Characteristics
Ensure the location, including passageways and elevators, can accommodate the size and weight of the ETX-1630x.
| Dimensions | 1053 mm × 679 mm × 1971 mm (41.5 in. × 26.7 in. × 77.6 in.) |
|---|---|
| Maximum weight as shipped |
ETX-16301: 473.35 kg (1043 lb) ETX-16309: 468.86 kg (1033 lb) |
| Acoustic emissions | 64 dB, 1 m away |
ETX-1630x Ventilation Clearances
Ventilation clearances are required to ensure proper airflow to the ETX-1630x. Ensure obstructions are outside the following clearance requirements.
| Left and right sides | 0 mm (0 in.) |
|---|---|
| ITA side | 0 mm (0 in.) |
| HMI side | 305 mm (12 in.) |
| Top | 508 mm (20 in.) |
ETX-16301/16309 Hardware Components
The following components are used within the ETX-16301/16309. Hardware component information is located in the ETX-16301/16309 User Manual and ETX-16301/16309 Specifications.
Pulser Components
The pulser can create brief, high current pulses that you can use to take measurements. The pulser includes a bias supply that can power a DUT in preparation to receive a pulse.
| Component Type | Model, NI Part Number | Resource Name | Ratings Override | PXI Chassis Slot | Mass Interconnect Slot |
|---|---|---|---|---|---|
| Pulse current multiplexer | RM-16061, 138834-01 |
PULSER_MUX1 | — | — | J11 and J12 |
| Electronic load | PEL-3111A, 756658A-01 |
PULSER_ELOAD1 | — | — | — |
| PEL-3211A (Quantity: 3), 756659A-01 |
PULSER_ELOAD_BOOSTER1 PULSER_ELOAD_BOOSTER2 PULSER_ELOAD_BOOSTER3 |
— | — | — | |
| Power supply | RMX-41011, 786006-01 |
PULSER_CHARGE_PPS1 | — | — | — |
| RMX-4122, 782857-01 |
PULSER_BIAS_PPS1 | — | — | — | |
| Power measurements conditioner | RM-26999, 786328-01 |
PULSER_PMC1 |
1500 V DC, Category I Supported transducers: DS50UB-10V DS200UB-10V DS600UB-10V DM1200UB-10V DL2000UB-10V |
— | J15 and J18 |
| Multifunction I/O | PXIe-6366, 781057-01 |
PULSER_SMIO | — | 16 | — |
| Current transducer | DM1200UB-10V, 788929-01 |
PULSER_TRANSDUCER1 | — | — | — |
Refer to Pulser Specifications for more information about the pulser.
Power Signals DAQ Components
Use the Power Signals DAQ to perform voltage and current measurements in the ETX-1630x.
| Component Type | Model, NI Part Number | Resource name | Ratings Override | PXI Chassis Slot | Mass Interconnect Slot |
|---|---|---|---|---|---|
| Multifunction I/O | PXIe-6368, 785926-01 |
PWRSIGDAQ1_SMIO1 | — | 17 | — |
| Power measurements conditioner | RM-26999 (Quantity: 2), 786328-01 |
PWRSIGDAQ1_PMC1 PWRSIGDAQ1_PMC2 |
1500 VDC, Category I Supported transducers: DS50UB-10V DS200UB-10V DS600UB-10V DM1200UB-10V DL2000UB-10V |
— | J15 and J18 |
| Current transducer | DS50UB-10V, 786956-01 |
PWRSIGDAQ1_TRANSDUCER1 | — | — | — |
Additional Components
The following components are independent of the composite instruments, and you can configure and use these components individually in the ETX-1630x. Additional components have an NI part number unless otherwise noted.
| Component type | Model, NI Part Number | Resource Name | Ratings Override | PXI Chassis Slot | Mass Interconnect Slot |
|---|---|---|---|---|---|
| PXI chassis | PXIe-1084, 784058-01 |
PXIChassis1 | — | — | — |
| PXI controller | PXIe-8862, Contact NI |
User-specified | — | 1 | — |
| Digital multimeter | PXIe-4082, 783131-01 |
DMM1 | ±60 V | 6 | J4 |
| PXIe-4082, 783131-01 |
DMM2 | ±300 V | 8 | J13 | |
| Multifunction I/O | PXIe-6366, 781057-01 |
SMIO1 | — | 12 | J17 |
| Power supply | PXIe-4112, 782857-01 |
PXI_PPS1 | — | 11 | J17 |
| RMX-41041, 786014-01 |
RMX_PPS1 | — | — | J6 | |
| EA-PS 11500-30[2]2 The ETX-16309 has a different power supply than
the other ETX models. Refer to ETX-16309 specific supplemental
documentation for more information.,
789716-01 |
HP_PPS1 | 1500 V, 30 A, 10 kW | — | J9 | |
| Source measure unit | PXIe-4139, 782856-02 |
SMU1 | — | 7 | J4 |
| Relay driver | PXI-2567, 778572-67 |
RELAY_DRIVER1 | 16 channels (CH0 through CH15) | 2 | J1 |
| Multiplexer | PXIe-2527, 780587-27 |
MUX1 | — | 9 | J13 |
| Matrix | PXIe-2737, 782835-37 |
MATRIX1 | — | 5 | J4 |
| Bank-isolated digital I/O module | PXI-6528, 778543-01 |
DIO1 | 32 channels (16 source/sink inputs in 2 banks, 16 source/sink outputs in 2 banks) | 3 | J1 |
| Analog output | PXIe-4322, 782878-01 |
AO1 | — | 13 | J17 |
| RS232 serial instrument control module | PXIe-8430/8, 781472-01 |
COM2 COM3 |
2-port | 4 | J1 |
| CAN/LIN | PXIe-8510, 784122-01 |
CAN1 CAN2 CAN3 CAN4 LIN5 LIN6 |
4 CAN channels 2 LIN channels[3]3 The CAN connection is through the TRC-8543, and the LIN connection is through the TRC-8546. |
18 | J17 |
Field Diagnostic Tester
Use the field diagnostic tester (FDT) and maintenance software to perform continuity checks for components within the system. The FDT generates reports and alerts you of discontinuity and reasonable shorts within the system.
| Component Type | Model | Resource Name | NI Part Number |
|---|---|---|---|
| FDT | FDT-16050 | N/A | 789858-01 |
ETX-16301/16309 Environmental Characteristics
| Operating temperature | 5 °C to 32 °C |
|---|---|
| Storage temperature | 0 °C to 60 °C |
| Operating humidity | 10% RH to 80% RH, noncondensing |
| Storage humidity | 5% RH to 80% RH, noncondensing |
| Pollution degree | 2 |
| Maximum altitude | 2000 m |
1 Neutral is applicable only for systems with the RMX-10140-50Y2P power entry panel.
2 The ETX-16309 has a different power supply than the other ETX models. Refer to ETX-16309 specific supplemental documentation for more information.
3 The CAN connection is through the TRC-8543, and the LIN connection is through the TRC-8546.