REM-11152 Pinout
- Updated2023-02-20
- 2 minute(s) read
REM-11152 Pinout
| Signal | Color | Description | |
|---|---|---|---|
| a1, a2 | Red | 24 VDC (UI) | Supply to digital input modules (internally jumpered) |
| b1, b2 | Blue | GND | Reference potential of the supply voltage (internally jumpered) |
| 00 to 07 | Orange | DI0...DI7 | Digital inputs 0 to 7 |
| 40 to 47 | Orange | DI8...DI15 | Digital inputs 8 to 15 |
| 10 to 17, 50 to 57 | Red | 24 VDC (US) | Sensor supply voltage output |
| 20 to 27, 60 to 67 | Blue | GND | Reference potential for all channels |
| 30 to 37, 70 to 77 | Green | FE | Functional earth ground (FE) |
| LED | LED Color | LED Pattern | Indication |
|---|---|---|---|
| D | Green | Solid | The REM-11152 is ready for operation. |
| Flashing | Data is invalid or unavailable. | ||
| Green/Yellow | Flashing | The REM-11152 cannot communicate with the connected devices. | |
| D | Yellow | Solid | The REM-11152 did not detect a valid cycle after power-on. |
| Flashing | The REM-11152 is not part of the configuration. | ||
| Red | Solid | The REM-11152 has lost connection to the Bus Coupler. | |
| Flashing | The REM-11152 has lost connection to the preceding adjacent module. | ||
| — | Off | The REM-11152 is in reset mode. | |
| UI | Green | Solid | Supply to digital output module present. |
| — | Off | No supply to digital output modules. | |
| E1 | Red | Solid | Breakdown or overload/short-circuit of an output. |
| — | Off | No I/O error. | |
| E2 | Red | Solid | Breakdown or overload/short-circuit of an output. |
| — | Off | No I/O error. | |
| 00 to 07, 40 to 47 | Red | Solid | Short-circuit/overload of the output. |
| Yellow | Solid | Input is set. | |
| — | Off | Input is not set. |