FPGA VIs
- Updated2025-12-23
- 1 minute(s) read
Owning Palette: Electrical Power VIs
Requires: Electrical Power Toolkit. This topic might not match its corresponding palette in LabVIEW depending on your operating system, licensed product(s), and target.
Use the FPGA VIs to measure electrical power data on FPGA targets.
| Palette Object | Description |
|---|---|
| FPGA Resampling | Resamples even-time-spaced voltage and current signals into even-angle-spaced signals. The input signals must have a sample rate of 50 kHz. The output signals are synchronous with the line frequency with a constant number of samples per cycle. Use the Resampling for Power Quality VI if you want to perform resampling on the host computer. You must manually select the polymorphic instance to use. This VI supports measuring single-bus single-line and single-bus multiple-line systems. |
| Subpalette | Description |
|---|---|
| Protection VIs | Use the Protection VIs to implement protection devices on FPGA targets. Protection devices measure input energizing quantities, set thresholds of pick-up signals, and delay for certain time intervals before trip signals assert. Protection devices also control the automatic reclosing and lockout of circuit breakers. |
| Synchrophasor VIs | Use the Synchrophasor VIs to perform synchrophasor measurement on FPGA targets. The Synchrophasor VIs are in compliance with IEEE Std C37.118.1-2011. |