Complete the following steps to synchronize multiple NI 9361 modules that are connected to the same FPGA device.

  1. Create the FPGA I/O items with all the I/O channels to be synchronized, within a single FPGA I/O Node. Otherwise, the FPGA I/O Node will not return synchronized data.
  2. Configure an FPGA I/O Node with Start channels for the NI 9361 modules you want to synchronize.
  3. Wire a Boolean constant set to TRUE to each Start channel.