Analog I/O Parameters (NI 9351 Only)
- Updated2024-05-17
- 1 minute(s) read
Analog I/O Parameters (NI 9351 Only)
When you select a configuration for a channel, the I/O Configuration table enables the appropriate parameters. Refer to the following table for the parameters associated with each configuration.
| Signal Type | Configuration | Parameters |
|---|---|---|
| Analog Inputs | Single input (1oo1) | Low low threshold, Low threshold, High threshold, High high threshold, Hysteresis |
| Dual input (1oo2) | Low low threshold, Low threshold, High threshold, High high threshold, Hysteresis, Discrepancy time, Discrepancy current | |
| Triple input (2oo3) | Low low threshold, Low threshold, High threshold, High high threshold, Hysteresis, Discrepancy time, Discrepancy current |