Safety Guidelines for Hazardous Locations
- Updated2022-05-02
- 1 minute(s) read
Safety Guidelines for Hazardous Locations
These products have been evaluated as Ex ec IIC T4 Gc equipment and are CCC certified. Each product is suitable for use within ambient temperatures of -40 °C ≤ Ta ≤ 70 °C in either nonhazardous locations or Zone 2 hazardous locations. If you are using the products in Gas Group IIC hazardous locations, you must use the device in an NI chassis that has been evaluated as Ex ec IIC T4 Gc equipment.
Follow these guidelines if you are installing the product in a potentially explosive environment. Not following these guidelines may result in serious injury or death.
Caution Do not disconnect
I/O-side wires or connectors unless power has been switched off or the area is known
to be nonhazardous.
Caution Do not remove
modules unless power has been switched off or the area is known to be nonhazardous.
Caution Substitution of
components may impair suitability for Zone 2.
Caution Transient protection
shall be provided that is set at a level not exceeding 140% of the peak rated
voltage value of 85 V at the supply terminals to the
equipment.
Caution The system shall
only be used in an area of not more than Pollution Degree
2, as defined in IEC/EN 60664-1.
Caution The system shall be
mounted in a CCC-certified enclosure with a minimum ingress protection rating of at least
IP54 as defined in GB/T3836.1.
Caution The enclosure must
have a door or cover accessible only by the use of a tool.