DAQmx Trigger (Start » Analog Edge) (G Dataflow)

Last Modified: September 18, 2017

Configures the task to start acquiring or generating samples when an analog signal crosses the level you specify.

connector_pane_image
datatype_icon

task in

task in is the name of the task that the operation applies.

datatype_icon

source

source is the name of a virtual channel or terminal where there is an analog signal to use as the source of the trigger.

For E Series devices, if you use a channel name, the channel must be the first channel in the task. The only terminal you can use for E Series devices is PFI0.

datatype_icon

slope

slope specifies on which slope of the signal to start acquiring or generating samples when the signal crosses level.

Name Description
Falling

Start acquiring or generating samples when the signal crosses level on a falling slope.

Rising

Start acquiring or generating samples when the signal crosses level on a rising slope.

datatype_icon

level

level specifies at what threshold to start acquiring or generating samples. Specify this value in the units of the measurement or generation. Use slope to specify on which slope to trigger at this threshold.

datatype_icon

error in

error in describes error conditions that occur before this node runs. This input provides standard 'error in' functionality.

datatype_icon

task out

task out is a reference to the task after this node runs.

datatype_icon

error out

error out contains error information. If error in indicates that an error occurred before this node ran, error out contains the same error information. Otherwise, error out describes the error status that this node produces.

Where This Node Can Run:

Desktop OS: Windows

FPGA: LabVIEW NXG does not support FPGA devices

Web Server: Not supported in VIs that run in a web application