Table Of Contents

DAQmx Export Signal (Most Signals) (G Dataflow)

Version:
    Last Modified: February 6, 2017

    Routes a control signal to the terminal you specify. The output terminal can reside on the device that generates the control signal or on a different device. You can use this node to share clocks and triggers among multiple tasks and devices. The routes this node creates are task-based routes.

    connector_pane_image
    datatype_icon

    task in

    task in is the name of the task that the operation applies.

    datatype_icon

    signal

    signal is the name of the trigger, clock, or event to export.

    Name Description
    10 MHz Reference Clock

    Output of an oscillator that you can use to synchronize multiple devices.

    20Mhz Timebase Clock

    Output of an oscillator that is the onboard source of the Master Timebase. Other timebases are derived from this clock.

    Advance Complete Event

    Signal a switch product generates after it both executes the command(s) in a scan list entry and waits for the settling time to elapse.

    Advance Trigger

    Trigger that moves a switch to the next entry in a scan list.

    AI Convert Clock

    Clock that causes an analog-to-digital conversion on a multiplexed device. One conversion corresponds to a single sample from one channel.

    AI Hold Complete Event

    Signal a multiplexed device generates when the device latches analog input data (the ADC enters "hold" mode), and it is safe for any external switching hardware to remove the signal, and replace it with the next signal. This event does not indicate the completion of the actual analog-to-digital conversion.

    Change Detection Event

    Signal a static DIO device generates when the device detects a rising or falling edge on any of the lines or ports you selected when you configured change detection timing.

    Counter Output Event

    Signal a counter generates. Each time the counter reaches terminal count, this signal toggles or pulses. This also applies to counter output tasks.

    Reference Trigger

    Trigger that establishes the reference point between pretrigger and posttrigger samples.

    Sample Clock

    Clock the device uses to time each sample.

    Start Trigger

    Trigger that begins a measurement or generation.

    Watchdog Timer Expired Event

    Signal a static DIO device generates when the watchdog timer expires.

    datatype_icon

    output terminal

    output terminal is the destination of the exported signal. A DAQmx terminal constant lists all terminals on installed devices. You can also specify a string containing a comma-delimited list of terminal names.

    datatype_icon

    error in

    error in describes error conditions that occur before this node runs. This input provides standard 'error in' functionality.

    datatype_icon

    task out

    task out is a reference to the task after this node runs.

    datatype_icon

    error out

    error out contains error information. If error in indicates that an error occurred before this node ran, error out contains the same error information. Otherwise, error out describes the error status that this node produces.