When you power on the cRIO-9038 for the first time, the device boots into safe mode. The POWER LED illuminates, the STATUS LED illuminates briefly, and then the STATUS LED blinks twice every few seconds. ...

Ensure that the environment in which you are using the cRIO-9038 meets the following specifications. Operating temperature (IEC 60068-2-1, IEC 60068-2-2) -40 °C to 70 °C Operating humidity (IEC 60068-2-78) ...

Verify that power is not connected to the I/O connector(s) on the C Series module before you remove a module from the cRIO-9038 . If the system is in a nonhazardous location, the cRIO-9038 can be powered ...

Caution Observe all instructions and cautions in the user documentation. Using the model in a manner not specified can damage the model and compromise the built-in safety protection. Return damaged models ...

Complete the following steps to set a system password. Note The default username for the cRIO-9038 is admin . There is no default password for the cRIO-9038 , so you must leave the password field blank ...

The following table describes the STATUS LED indicators. Table 3. STATUS LED Indicators LED Color LED Pattern Indication Yellow Blinks twice and pauses The cRIO-9038 is in safe mode. Software is not installed, ...

Software is licensed pursuant to the software license agreements provided with the software or, in the absence of such license agreements, the National Instruments Software License Agreement available ...

The following figure shows the reset behavior of the cRIO-9038 . Figure 3. Reset Button Behavior Press and hold RESET button fo r ≥ 5 s Press and hold RESET button for < 5 s Run Mode Safe Mode Press

Notice To prevent electrostatic discharge (ESD) from damaging the device, ground yourself using a grounding strap or by holding a grounded object, such as your computer chassis. Touch the antistatic package ...

Put the cRIO-9038 in safe mode and enable the RS-232 serial port by holding the RESET button down for 5 seconds. The STATUS LED starts blinking three times every few seconds. Use the RS-232 serial port ...

Verify that the following items are included in the cRIO-9038 kit. Parent topic: Overview Parent topic: GSG Purpose (cRIO/sbRIO)

This document lists the specifications for the National Instruments cRIO-9038 . The following specifications are typical for the -40 °C to 70 °C operating temperature range unless otherwise noted. Caution ...

This document describes how to begin using the NI cRIO-9039 and NI cRIO-9039 Sync . In this document, the NI cRIO-9039 and NI cRIO-9039 Sync are inclusively referred to as the cRIO-9039 . For more information ...

Complete the following steps to install a C Series module. 3 2 2 1 1: 1: P P O O W W E E R R 2 2 : S : S T T A A T T US US

Complete the following steps to find the system in MAX. Launch MAX on the host computer. Expand Remote Systems in the configuration tree and locate your system. Select your target. Tip MAX lists the system ...

Add an exception for MAX to your network firewall or other security software by completing the following steps: On Windows 7, select Start » Control Panel » System and Security » Windows Firewall » Allow ...

You must connect the cRIO-9039 grounding terminal to the grounding electrode system of the facility. What to Use Ring lug Wire, 1.3 mm 2 (16 AWG) or larger Screwdriver, Phillips #2 What to Do Complete ...

The cRIO-9039 requires a 9 V to 30 V external power supply. The cRIO-9039 filters and regulates the supplied power and provides power for the C Series modules. The cRIO-9039 has a primary power input, ...

The cRIO-9039 has the following connectors, LEDs, and buttons. Parent topic: Overview Parent topic: GSG Purpose (cRIO/sbRIO)