The External Link: Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 document, also known as the 9-2LE, defines four kinds of SMV stream types:
The NI cRIO-906x series only supports the 80 samples per cycle (50Hz) and 80 samples per cycle (60Hz) SMV stream types, whereas the NI cRIO-903x supports all four kinds of SMV streams.