當在MAX中加入無線C-Series模組時出現Error -201247
主要軟體:
主要軟體版本: 8.8
主要軟體修正版本:
次要軟體: N/A
硬體: CompactRIO>>Analog Input Modules>>NI 9233
問題: 我有一組WLS-9163上面插著C-Series的模組,但是我在MAX中都無法順利安裝驅動程式,且會出現下列錯誤訊息:
Error -201247 occurred at Add Networked DAQ Devices...
Possible reason(s):
Measurements: Device cannot be created in MAX because a driver could not be found for the device. You may need to upgrade NI-DAQmx.
我已經安裝了DAQmx 8.8的驅動程式。
解答: 這樣的錯誤訊息會發生於您的WLS-9163上插著不支援的C-Series模組,因為並不是所有的C-Series模組都支援,下方列出目前WLS-9163所支援的C-Series模組:
- NI 9211 (4-channel, 14 S/s, 24-bit, ±80 mV thermocouple input)
- NI 9215 (4-channel, 100 kS/s/ch, 16-bit, ±10 V analog input)
- NI 9219 (4-channel, 100 S/s/ch, 24-bit, ±60 V, ±25 mA universal input)
- NI 9234 (4-channel, 51.2 kS/s/ch, 24-bit, ±5 V IEPE input)
- NI 9237 (4-channel, 50 kS/s/ch, 24-bit, ±25 mV/V bridge and strain input)
相關連結:
附加檔案:
報告日期: 10/21/2008
最後更新: 12/04/2008
文件偏號: 4QK6SL53