Not every issue known to NI appears on this list; it is intended to show the most severe and common issues that you may encounter and provide workarounds when possible. Other technical issues that you may encounter could occur through normal product use or system compatibility issues. You may find more information on these issues in NI’s Product Documentation, Knowledgebase, or Community.
|
Bug Number |
Legacy ID |
Description |
Details |
|---|---|---|---|
| 453982 |
Windows Throws a Blue Screen Error When a PXI-653x Card is Deleted in NI MAXWindows may throw a blue screen error when a PXI-653x card is deleted in NI MAX while a project that has one or more channels configured on that card is open in FlexLogger. This error occurs because FlexLogger is running a task and the driver does not correctly handle the interruption.
Workaround: Close the FlexLogger project before deleting a PXI-653x card in NI MAX.
|
Reported Version: FlexLogger 2021 R3 Resolved Version: N/A Added: Jul 27, 2021 |
|
| 1695510 |
Run Button Remains Disabled After Changing a Logging Specification SettingThe Run
button may remain disabled after you change a setting in the Logging Specification. Workaround: Click anywhere in the
application to re-enable the Run button. |
Reported Version: FlexLogger 2021 R4 Resolved Version: N/A Added: N/A |
|
| 1664955 |
FlexLogger Throws an Error When Multiple Alarms Trigger Rapidly and RegularlyFlexLogger may throw a compile error when running
a test where multiple alarms trigger rapidly and regularly. This can happen when
using a simulated device. The periodic nature of the simulated signals causes alarms
to trigger every second. The compile error states the following: "An unexpected error related to alarm
processing has occurred. It is recommended you restart FlexLogger or contact NI
support at ni.com/support."
Workaround: Ignore the error and
continue to run your test. Alternatively, you can stop the test and FlexLogger will
clear the error. |
Reported Version: FlexLogger 2021 R4 Resolved Version: N/A Added: N/A |
|
| 1665871 |
Python API Method TestSession.start() Returns True When a Test Has Not StartedWhen you call the Test
Session.start() Python API method while FlexLogger is reconfiguring channels, the
method may incorrectly return True, indicating that the test has started
successfully when it has not. This can happen when FlexLogger is loading
a project. Workaround: Call TestSession.start() and then query TestSession.state to confirm the test has started. Run this logic in a loop until the test starts. The code is provided below. |
Reported Version: FlexLogger 2021 R3 Resolved Version: N/A Added: N/A |
Issues found in this section will not be listed in future known issues documents for this product.
There are currently no issues to list.
Explore Support Content and Product Documentation
Ask the NI Community
Request Support from an Engineer
A valid service agreement may be required, and support options vary by country