The following items are known issues in InsightCM Enterprise 1.0 sorted by Category.
ID | Known Issue | |||||
---|---|---|---|---|---|---|
InsightCM Condition Monitoring Systems | ||||||
501153 Return |
CMS-9074 Devices Sometimes Fails to Detect 9205 Module in Slot 7 This causes the device to not come online since it is missing a module. Workaround: Reboot the CMS-9074 then save the Device Configuration.
|
|||||
501335 Return |
Some Data Can be Lost if a CMS-9024 Disconnects While Streaming If a CMS-9024 is disconnected for more than 3 minutes while streaming, a new stream will be started if it reconnects later on while still in the streaming conditions. Two partial streams will end up stored on the server, one before the disconnect, and one after the disconnect. Data collected while the cRIO was disconnected will be lost. Workaround: N/A
|
|||||
512907 Return |
Alarms improperly transition between states when on or off delays are configured This can be observed if the feature the alarm is triggered off of is close to the set point of the alarm. The alarm on and off delays do not prevent the alarm from transitioning. Workaround: This issue has been fixed in the InsightCM 1.0.0f1 Patch. See InsightCM 1.0.0 Patch Details for more information.
|
|||||
InsightCM Data Explorer | ||||||
495198 Return |
Data Explorer Crashes if the Trend Viewer X Axis is Changed to Logarithmic The viewers in Data Explorer inherit the native DIAdem feature to change X axis scaling to logarithmic. If this is done to the trend viewer it will crash Data Explorer. Workaround: N/A
|
|||||
502166 Return |
Data Explorer Error: "DataFinder query returned an error. This can be caused by malformed or invalid data files" This error happens because DataFinder was unable to complete it's query in less than 15 seconds. Query times are effected by several variables, common causes of long query times are: large DataFinder indexes, limited CPU resources and disk access time. Workaround: Reduce the amount of TDMS of files that DataFinder has to index to improve query times. If this isn't possible contact National Instruments. This issue has been fixed in the InsightCM 1.0.0f1 Patch. See <a href="http://digital.ni.com/public.nsf/allkb/FBC22C1E22942E7786257DD90061BD93?OpenDocument">InsightCM 1.0.0 Patch Details</a> for more information.
|
|||||
506760 Return |
Waterfall Viewer Clears When Data is Manually Refreshed The Waterfall Viewer curves are removed if the Data Explorer's data is refreshed by View>Refresh action. Workaround: To recover the viewer, use the "Clear All Viewers" button, then reconfigure the waterfall viewer.
|
|||||
509735 Return |
Data Explorer Meta Data Pane Does Not Update Units for Waterfall Viewer The units shown in the Meta Data Pane do not always reflect the units displayed on the Waterfall viewer's axes. This will happen using integration or differentiation to change the Y axis units away from the channel's native units. Additionally this will happen if the X axis units are changed from Hz to CPM or Orders. Workaround: The Waterfall Viewer units are the correct units. The normal FFT Viewer does not have this problem. This issue has been fixed in the InsightCM 1.0.0f1 Patch. See <a href="http://digital.ni.com/public.nsf/allkb/FBC22C1E22942E7786257DD90061BD93?OpenDocument">InsightCM 1.0.0 Patch Details</a> for more information.
|
|||||
537793 Return |
Waterfall Viewer Clears When Data is Manually Refreshed The Waterfall Viewer curves are removed if the Data Explorer's data is refreshed by View>Refresh action. Workaround: To recover the viewer, use the "Clear All Viewers" button, then reconfigure the waterfall viewer.
|
|||||
InsightCM Systems Manager | ||||||
485592 Return |
Using Delete Key to Delete a Curve From the Waterfall Viewer Crashes Data Explorer In the Data Explorer curve legend it's possible to select a curve and use the delete key to remove the curve. If this is done to a curve in the Waterfall Viewer it will crash Data Explorer. Workaround: N/A
|
|||||
487238 Return |
Device Has Error Status on Dashboard If a module is ever removed from a slot that has configured channels, the device will report back to the server an error state. The device will not automatically recover if the module is placed back and rebooted Workaround: After replacing the module and rebooting the device, the device configuration in the Systems Manager must be saved.
|
|||||
488672 Return |
Connection Info Sometimes Contains Incorrect IP address of InsightCM Server InsightCM identifies it's own IP address when it sends Connection information to a device. In rare circumstances this information can be incorrect. Workaround: In the Systems Manager Reset the Connection from the Devices page. If problem persists contact National Instruments.
|
|||||
488925 Return |
Configurations On Device Not Updated When Imported Alarms Make Changes to Device's Rules A device's alarm rules can be modified when alarm rules are imported on the Alarm Panel page. The actual device will not have updated configurations sent to it. Workaround: Open the device's configuration page and save the configuration to send the updated alarm rules to the device.
|
|||||
493283 Return |
PI Historian ServiceDidNotRespond Error While Processing Data Historian page will sometimes fail to load on InsightCM systems with many Devices and PI Points and all Devices acquire at the same time. The Historian service prioritizes updating PI tags over displaying updates to Systems Manager Workaround: Historian page will load when it is done processing acquired data.
|
|||||
494133 Return |
Historian ServiceDidNotRespond error on PI Point Query ServiceDidNotRespond errors can occur if the query string is to broad and the PI server has many points. For example a query of "tag='*'" will return all points for a server and the query times out. Workaround: Make queries to PI Server more specific to reduce the amount of results. InsightCM can only display 1000 PI point results.
|
|||||
494312 Return |
Stream Data Won't be Processed if More than 8 Devices Stream at the Same Time By default InsightCM can only handle 8 simultaneous streaming at the same time. Any additional streams will not be processed by InsightCM Workaround: see KB on how to enable more analysis instances
|
|||||
505431 Return |
Equipment Layout Information at Wrong Level when Imported from Spreadsheet The Enterprise level of the Equipment Layout is created when the Equipment Layout page is loaded for the first time after installation. This will cause importation problems if a Devices Spreadsheet with Equipment Layout information is imported before the Enterprise level has been created. Workaround: Navigate to the Equipment Layout page once before importing a Device Spreadsheet with equipment layout for the first time.
|
|||||
506363 Return |
Alarm Rules Not Transferred When a Template is Applied to an Existing Device If a template is saved for a device that has alarm rules configured, the alarm rules will not be created when the template is applied to an already configured device. Alarm Rules are applied when a template is used on a new device. Workaround: Instead of applying the template to an existing device, add a new device and apply the template during the initial configuration wizard.
|
|||||
509554 Return |
Systems Manager Exports Incorrectly Named Connection File The Connection file exported by the Systems Manager's Devices page will use the Device name instead of the Hardware name for the file name. This causes the desired cRIO to not recognize the file when place on a USB stick. Workaround: Manually rename the Connection file to match the device's Hardware name. This name will be the same as the cRIO's host name.
|
|||||
511151 Return |
InsightCM tag aging service crashes and can cause other services to hang The InsightCM tag aging service deletes old cRIO status information each night at 1:15 am. On InsightCM systems with many connected devices this service can crash and cause other services to hang. This will prevent users from logging into the InsightCM Systems Manager. Workaround: This issue has been fixed in the InsightCM 1.0.0f1 Patch. See InsightCM 1.0.0 Patch Details for more information.
|
Document last updated on 12/7/2015