Specifies how to count and interpret the pulses the encoder generates on signal A and signal B. X1, X2, and X4 are valid for quadrature encoders only. Two Pulse Counting is valid for two-pulse encoders only.
X2 and X4 decoding are more sensitive to smaller changes in position than X1 encoding, with X4 being the most sensitive. However, more sensitive decoding is more likely to produce erroneous measurements if vibration exists in the encoder or other noise exists in the signals.
Data type:
Name | Value | Description |
---|---|---|
X1 | 10090 | If signal A leads signal B, count the rising edges of signal A. If signal B leads signal A, count the falling edges of signal A. |
X2 | 10091 | Count the rising and falling edges of signal A. |
X4 | 10092 | Count the rising and falling edges of signal A and signal B. |
Two Pulse Counting | 10313 | Increment the count on rising edges of signal A. Decrement the count on rising edges of signal B. |
Where This Property Is Available:
Desktop OS: Windows
FPGA: Not supported
Web Server: Not supported in VIs that run in a web application