The NI 9361 counter input module supports the following measurement types:
-
Duty cycle
-
Event counting
-
Encoder position
-
Frequency
-
Period
-
Pulse width
-
Velocity
The NI 9361 has eight counters and supports adding multiple counter channels to the same task. A single task can have different measurement types. Multiple counter module channels can be added to the same task.
Note
-
You cannot mix module and chassis counters in the same task.
-
You cannot use the chassis counter through the counter module.
-
You cannot create multiple counter tasks with a single NI 9361.
-