Table Of Contents

Analog I/O Parameters (NI 9351 Only)

Version:
    Last Modified: May 15, 2018

    When you select a configuration for a channel, the I/O Configuration table enables the appropriate parameters. Refer to the following table for the parameters associated with each configuration.

    Table 1. I/O Configuration Parameters
    Signal Type Configuration Parameters
    Analog Inputs Single input (1oo1) Low low threshold, Low threshold, High threshold, High high threshold, Hysteresis
    Dual input (1oo2) Low low threshold, Low threshold, High threshold, High high threshold, Hysteresis, Discrepancy time, Discrepancy current
    Triple input (2oo3) Low low threshold, Low threshold, High threshold, High high threshold, Hysteresis, Discrepancy time, Discrepancy current