Table Of Contents

Analog Configurations (NI 9351 Only)

Version:
    Last Modified: May 15, 2018

    The NI 9351 has four analog input channels. You can use them to create the following configurations.

    Table 1. Analog Configurations
    Configuration Channels Notes
    Single input (1oo1) Available on any analog input channel. Monitors current ranges for a single analog signal.
    Dual input (1oo2) A dual input configuration available on the following channel pairs: [AI0, AI1] and [AI2, AI3]. Establishes a 1oo2 voting strategy on two analog input channels. Configuring AI0 reserves AI1 and configuring AI2 reserves AI3.
    Triple input (2oo3) A triple input configuration is only available on AI0. Establishes a 2oo3 voting strategy on three analog input channels. Configuring AI0 reserves AI1 and AI2.
    spd-note-note
    Note  

    Dual input (1oo2) configurations are only available on the even-numbered channel. Only the even-numbered channel will be available in the Faults table or on the state machine diagram.

    spd-note-note
    Note  

    A triple input (2oo3) configuration is only available on AI0. Only AI0 will be available in the Faults table or on the state machine diagram.