STATUS LED Indicators

The following table lists the STATUS LED indicators.
Table 1. STATUS LED Indicators
LED Pattern Indication
Blinks twice and pauses

The sbRIO-9607 is in safe mode. Software is not installed, which is the factory default state, or software has been improperly installed on the sbRIO-9607.

An error can occur when an attempt to upgrade the software is interrupted. Reinstall software on the sbRIO-9607. Refer to the Measurement & Automation Explorer (MAX) Help for information about installing software on the sbRIO-9607.

Blinks three times and pauses

The sbRIO-9607 is in user-directed safe mode, or the sbRIO-9607 is in install mode to indicate that software is currently being installed.

This pattern may also indicate that the user has forced the sbRIO-9607 to boot into safe mode by pressing the reset button for longer than five seconds or by enabling safe mode in MAX. Refer to the Measurement & Automation Explorer (MAX) Help for information about safe mode.

Blinks four times and pauses

The sbRIO-9607 is in safe mode. The software has crashed twice without rebooting or cycling power between crashes.

Continuously blinks

The sbRIO-9607 has not booted into NI Linux Real-Time. The sbRIO-9607 either booted into an unsupported operating system, was interrupted during the boot process, or detected an unrecoverable software error.

On momentarily The sbRIO-9607 is booting. No action required.
Off

The sbRIO-9607 is in run mode. Software is installed and the operating system is running.