Connecting Linear Voltage Input Signals

Figure 8. Linear mV Voltage Connection

1378

Figure 9. Linear VDC Voltage Connection

1378

  • Connect sensors to each channel which supply a linear voltage in ranges of ±100 mV or ±5 VDC.
  • For mV sensors, cable lengths of up to 250 m (820 ft.) are possible.
  • For VDC sensors, use shielded twisted sensor cables no longer than 5 m (16 ft.).