Connection Guidelines
Note For information about fuse ratings for the REM-11120, refer to the device datasheet on ni.com/manuals.
- Make sure that devices you connect to the REM-11120 are compatible with the module specifications.
- Push the wire into the terminal when using a solid wire or a stranded wire with a ferrule.
- Open the terminal by pressing a screwdriver into the spring lever when using a stranded wire without a ferrule.
- Use encapsulated thermocouples.
- Always connect the thermocouples using twisted pair equalizing conductors.
- Use shielded twisted pair equalizing conductors for a cables longer than 10 m (32 ft.).
- For mV sensors in environments prone to interference or sensor cables longer than 10 m (32 ft), use shielded twisted connecting cables.
- For thermocouple sensors, use shielded thermocouple connecting cables.
- NI recommends using the NI Remote I/O Shield Set for optimal shield connection.
- For installation in a cabinet, connect the cable shield to functional earth ground immediately after the cables enter the cabinet.