Replacing the RMX-4122
- Updated2025-10-31
- 2 minute(s) read
Learn how to replace the RMX-4122 power supply (part number 784763-01) in the ETX-1630x.
Equipment
- Torque driver, N · m or lb · in.
- #2 Phillips head bit
- Torque wrench, N · m or lb · in.
- 8 mm socket wrench bit
- 8 mm wrench
- Flathead screwdriver
- #1 Phillips head screwdriver
- Tray for loose fastening hardware
Torque the fasteners to the following specifications:
- M5 hex head: 2.49 N · m (22.0 lb · in.)
- 10-32 pan head: 3.16 N · m (27.9 lb · in.)
- Follow all Before Maintenance or Repair procedures.
- While facing the mass interconnect, unlock the door above the mass interconnect and pull the door open.
- Remove the safety cover from the output terminals of the RMX-4122 using the #1 Phillips head screwdriver.
- Loosen and remove the output terminal M5 nuts and bolts using the 8 mm wrench.
- Note where each cable is connected to the back of the RMX-4122, then remove all cables from back of the RMX-4122.
-
While facing the monitor and keyboard, complete the following steps:
- Tilt the monitor down.
- Unfasten the 10-32 screws securing the top filler panel to the rack and set aside the filler panel.
- Locate the S-brackets holding the front of the RMX-4122 to the vertical rack rails.
- Unfasten the 10-32 screws from the rack rail mounts using the #2 Phillips head bit.
-
Using the rails that support the RMX-4122, pull the RMX-4122 forward through the front
of the rack to remove it.
If necessary, remove the monitor from the monitor mount to facilitate removal of the RMX-4122.
Note Align the RMX-4122 with Rack U 37.
Note Use the L-brackets to rest the power supply during
installation.