Hard-Wired PEP Connection Specifications
- Updated2025-07-11
- 3 minute(s) read
Hard-Wired PEP Connection Specifications
MAINs power connections for ATE Core Configurations Generation 2 systems containing RMX-10140-32D2 3-Phase 32 A Delta PEPs, RMX-10140-50D2P 3-Phase 50 A Delta PEPs, and RMX-10140-50Y2P 3-Phase 50 A Wye PEPs must be hard-wired.
Notice Use only copper conductors for hard-wired
PEP connections.
RMX-10140-32D2 Power Connection Specifications
Note RMX-10140-32D2 placement on an ATE-38U/44U or ATE-38E is shown in the previous diagram. This PEP is also
compatible with the ATE-15U.
Figure Callout | Component | Tool | Description |
---|---|---|---|
1 | Input protective enclosure | 3 mm hex driver with 1.3 N · m (11.5 in. · lb) torque for screws | Enclosure for hard-wired power connections to the PEP. |
2 | M4 screw thread input terminal block | #2 Phillips screwdriver with 1.2 N · m to 1.8 N · m (10.6 in. · lb to 15.9 in. · lb) torque | Input terminal block for connecting hard-wired MAINs power to the
PEP. Note Use 22 AWG to 8 AWG wire, stripped to 8.0 mm (0.3 in.). |
3 | Earth termination mechanical lug | 3/16 hex driver with 5.1 N · m (45.0 in. · lb) torque | GND terminal for input power. Note Use 14 AWG to 2/0 AWG wire, stripped to 15.7 mm (0.6 in.). |
4 | Cable inlet grommet | N/A | Heyco M4848 15.0 mm to 25.4 mm (0.6 in. to 1 in.) grommet. |
RMX-10140-50D2P Power Connection Specifications
Figure Callout | Component | Tool | Description |
---|---|---|---|
1 | Input protective enclosure | 3 mm hex driver with 1.3 N · m (11.5 in. · lb) torque for screws | Enclosure for hard-wired power connections to the PEP. |
2 | Earth termination mechanical lug | 3/16 hex driver with 5.1 N · m (45.0 in. · lb) torque | GND terminal for input power. Note Use 14 AWG to 2/0 AWG wire, stripped to 15.7 mm (0.6 in.). |
3 | M6 screw thread input terminal block | #2 Phillips screwdriver with 2.5 N · m to 3.0 N · m (22.1 in. · lb to 26.6 in. · lb) torque | Input terminal block for connecting hard-wired MAINs power to the
PEP. Note Use 14 AWG to 2 AWG wire, stripped to 14.0 mm (0.6 in.). |
4 | Insulator termination for Neutral | 4 mm hex driver with 2.8 N · m (25.0 in. · lb) torque | Isolation terminal for power input neutral wires. |
5 | Cable inlet grommet | N/A | Heyco M4860 22.0 mm to 32.0 mm (0.9 in. to 1.2 in.) grommet |
RMX-10140-50Y2P Power Connection Specifications
Figure Callout | Component | Tool | Description |
---|---|---|---|
1 | Input protective enclosure | 3 mm hex driver with 1.3 N · m (11.5 in. · lb) torque for screws | Enclosure for hard-wired power connections to the PEP. |
2 | Earth termination mechanical lug | 3/16 hex driver with 5.1 N · m (45.0 in. · lb) torque | GND terminal for input power. Note Use 14 AWG to 2/0 AWG wire, stripped to 15.7 mm (0.6 in.). |
3 | M6 screw thread input terminal block | #2 Phillips screwdriver with 2.5 N · m to 3.0 N · m (22.1 in. · lb to 26.6 in. · lb) torque | Input terminal block for connecting hard-wired MAINs power to the
PEP. Note Use 14 AWG to 2 AWG wire, stripped to 14.0 mm (0.6 in.). |
4 | Cable inlet grommet | N/A | Heyco M4860 22.0 mm to 32.0 mm (0.9 in. to 1.2 in.) grommet |