The following diagrams show the locations and specifications of single phase RMX-10140 power entry panel features.

Notice Listed PEP voltage ratings represent the full input rating of the PEP. When integrated into a system with equipment with a more narrow input range, the input label of the PEP must be modified. There are labels included in the replacement kit. When replacing a PEP, match the label to the PEP you are replacing and affix it to the front of the new PEP, covering the PEP ratings label. After the label has been affixed, the new PEP can be installed in the system.
Note RMX-10140 PEPs are mounted in the ATE Core Configurations Generation 2 frame using M5 x 8 mm screws at the corners of the PEP.
Figure 13. RMX-10140-16S2 and RMX-10140-24S2 Block Diagram


RMX-10140-16S2 Single-Phase PEP

Figure 14. RMX-10140-16S2 Features
Figure Callout Name Description
1 Functional earth terminal Optional functional earth terminal for connection to facility GND. It is not required to connect to the functional earth terminal since the input power connector is industrial-rated with a reliable GND connection.
2 Input power connector IEC 60309, P+N+E, 20 A, 250 V, 6H inlet connector.
3 Main disconnect branch breaker 20 A rated branch input breaker.
4 Low-voltage digital communication ports Ports used for digital communication to and from the RCU and auxiliary equipment.
5 UPS loopbacks with functional earth terminal Optional UPS connection to provide backup power to the RCU and equipment in the rack.
6 PDU1 C19 outlet Distributes rack power through connection to RMX-10151 Single-Phase PDU or direct connection to high-power equipment.
7 C13 AUX outlets (x2) Power outlets which remain powered on during an EMO event.
8 AC RCU power outlet Internal AC power outlet reserved for sending power to the AC/DC power supply for the RCU.
9 AC fan panel power outlet Internal AC power outlet reserved for sending power to the AC/DC power supply for the fan panels.
10 Protective earth terminal M6 screw protective earth terminal directly connected to the input connector Earth GND terminal. This protective earth terminal should be connected to the main GND bus bar of the ATE Core Configurations Generation 2 system.
Note The UPS, C13 AUX outlets, and AC RCU power outlet remain powered on during EMO events. The C13 AUX outlets do not remain powered if the EMO event is caused by an overtemperature thermal fault.
Table 11. RMX-10140-16S2 Power Cable Options
Part Number Description
788846-03 Power Cord, AC, IEC 60309 Blue, 6H, 16A, P+N+E Connector to CEE7/7 3P, 3.0 m
788847-03 Power Cord, AC, IEC 60309 Blue, 6H, 16A, P+N+E Connector to NEMA 5-20P, 3.0 m
788848-01 Power Cord, AC, IEC 60309 Blue, 6H, 16A, P+N+E Connector to IEC C20, 12"
Figure 15. RMX-10140-16S2 Pin and Sleeve Connector


Part Number 788849-01[1]1 The Mennekes part number for this part is ME 320C6-180.
Description IEC 60309 Blue, 6H, 16/20A, P+N+E Pin and Sleeve Connector
Figure 16. RMX-10140-16S2 Single-Phase PEP Fuses
  1. Double pole fuses feeding RCU power, C13 AUX power, and fan power
  2. Input double pole fuses
Table 12. 16A Single Phase PEP Fuses
Callout Fuse Specification Value
1 Double pole fuses, RCU power, C13 AUX power, and fan power Current rating 6.3 A
Minimum voltage range 240 V
Voltage rating 440 V
Size 3AB, 6.3 mm × 32 mm
Fuse type Time-lag
Recommended replacement Littelfuse 35616300029
2 Double pole fuses, input Current rating 20 A
Minimum voltage range 240 V
Voltage rating 600 V
Size 5 mm × 20 mm
Fuse type Time-lag
Recommended replacement Bel Fuse 0ADKC9200-BE

RMX-10140-24S2 Single-Phase PEP

Figure 17. RMX-10140-24S2 Features
Figure Callout Name Description
1 Functional earth terminal Optional functional earth terminal for connection to facility GND. It is not required to connect to the functional earth terminal since the input power connector is industrial-rated with a reliable GND connection.
2 Input power connector IEC 60309, P+N+E, 30 A, 250 V, 6H inlet connector.
3 Main disconnect branch breaker 30 A rated branch input breaker.
4 Outlet branch breaker Double-pole, 20 A branch-rated breaker which supplies power to the PDU1 C19 outlet, RCU power outlet, fan power outlet, UPS interface, and AUX power C13 outlets.
Notice Per 61010-1 requirements, any power that exits the rack frame must be protected by a 20 A branch-rated breaker. Ensure that external power is only supplied from the RMX-10151 Single-Phase PDU connected to the PDU1 C19 outlet in the primary rack.
5 UPS loopbacks with functional earth terminal Optional UPS connection to provide backup power to the RCU and equipment in the rack.
6 PDU2 C19 outlet Distributes rack power through connection to RMX-10151 Single-Phase PDU or direct connection to high-power equipment.
7 PDU1 C19 outlet Distributes rack power through connection to RMX-10151 Single-Phase PDU. PDU1 power can be routed outside of the rack frame.
8 C13 AUX outlets (x2) Power outlets which remain powered on during an EMO event.
9 Protective earth terminal M6 screw protective earth terminal directly connected to the input connector Earth GND terminal. This protective earth terminal should be connected to the main GND bus bar of the ATE Core Configurations Generation 2 system.
10 AC fan panel power outlet Internal AC power outlet reserved for sending power to the AC/DC power supply for the fan panels.
11 AC RCU power outlet Internal AC power outlet reserved for sending power to the AC/DC power supply for the RCU.
12 Low-voltage digital communication ports Ports used for digital communication to and from the RCU and auxiliary equipment.
Table 13. RMX-10140-24S2 Power Cable Options
Part Number Description
789895-01 Power Cord, AC, IEC 60309 Blue, 6H, 24A, P+N+E Connector to IEC 60309 Blue, 6H, 24A, P+N+E Connector, 2.5 m
789896-2R5 Power Cord, AC, IEC 60309 Blue, 6H, 24A, P+N+E Connector to NEMA L6-30, 2.5 m
Figure 18. RMX-10140-24S2 Pin and Sleeve Connector


Part Number 789897-01[2]2 The Mennekes part number for this part is ME 330C6-122.
Description IEC 60309 Blue, 6H, 30/32A, P+N+E Pin and Sleeve Connector
Figure 19. RMX-10140-24S2 Single-Phase PEP Fuses
  1. Double pole fuses feeding RCU power, C13 AUX power, and fan power
  2. Input double pole fuses
Table 14. 24A Single Phase PEP Fuses
Callout Fuse Specification Value
1 Double pole fuses, RCU power, C13 AUX power, and fan power Current rating 6.3 A
Minimum voltage range 240 V
Voltage rating 440 V
Size 3AB, 6.3 mm × 32 mm
Fuse type Time-lag
Recommended replacement Littelfuse 35616300029
2 Double pole fuses, input[3]3 Fuses F2 and F4 fuse the C19 outlet labeled PDU 2. Fuses F1 and F3 fuse all other outlets. Current rating 20 A
Minimum voltage range 240 V
Voltage rating 600 V
Size 5 mm × 20 mm
Fuse type Time-lag
Recommended replacement Bel Fuse 0ADKC9200-BE

Single-Phase RMX-10140 PEP Power Requirements

Notice The product has been tested for power supply voltage fluctuations of ±10%.
Power Specification RMX-10140-16S2 RMX-10140-24S2
Input power rating Connector IEC 60309 20A IEC 60309 30A
Overvoltage category II II
Branch circuit rating 20 A 30 A
Voltage rating 100 V AC to 240 V AC 100 V AC to 240 V AC
Frequency 50/60 Hz 50/60 Hz
Current rating 16 A 24 A
Primary power outputs Connector C19 (x1) C19 (x2)
Voltage Same as input Same as input
Current rating 16 A per output 16 A per output
Frequency Same as input Same as input
EMO status Disabled during EMO Disabled during EMO
AUX power outputs Connector C13 (x2) C13 (x2)
Voltage Same as input Same as input
Current rating 2.5 A maximum 2.5 A maximum
Frequency Same as input Same as input
EMO status On during EMO On during EMO
Fan power output Connector Molex-style, 2-pin Molex-style, 2-pin
Voltage Same as input Same as input
Power rating 250 W 250 W
Frequency Same as input Same as input
Current rating Double pole fused at 6.3 A Double pole fused at 6.3 A
EMO status Disabled during EMO Disabled during EMO
Rack control unit (RCU) power output Connector Molex-style, 3-pin Molex-style, 3-pin
Voltage Same as input Same as input
Power rating 150 W 150 W
Frequency Same as input Same as input
Current rating Double pole fused at 6.3 A Double pole fused at 6.3 A
EMO status On during EMO On during EMO
Notice The PEP AUX power outlets remain on during an EMO event unless the event is caused by an overtemperature thermal fault. Ensure that they are only used to power safety-related devices and computer systems performing logging and error recovery. Total power should not exceed 250 W. Ensure that the connected equipment adheres to local regulations.

1 The Mennekes part number for this part is ME 320C6-180.

2 The Mennekes part number for this part is ME 330C6-122.

3 Fuses F2 and F4 fuse the C19 outlet labeled PDU 2. Fuses F1 and F3 fuse all other outlets.