Single Phase RMX-10140 Features
- Updated2025-07-11
- 7 minute(s) read
The following diagrams show the locations and specifications of single phase RMX-10140 power entry panel features.
RMX-10140-16S2 Single-Phase PEP
Figure Callout | Name | Description |
---|---|---|
1 | Functional earth terminal | Optional functional earth terminal for connection to facility GND. It is not required to connect to the functional earth terminal since the input power connector is industrial-rated with a reliable GND connection. |
2 | Input power connector | IEC 60309, P+N+E, 20 A, 250 V, 6H inlet connector. |
3 | Main disconnect branch breaker | 20 A rated branch input breaker. |
4 | Low-voltage digital communication ports | Ports used for digital communication to and from the RCU and auxiliary equipment. |
5 | UPS loopbacks with functional earth terminal | Optional UPS connection to provide backup power to the RCU and equipment in the rack. |
6 | PDU1 C19 outlet | Distributes rack power through connection to RMX-10151 Single-Phase PDU or direct connection to high-power equipment. |
7 | C13 AUX outlets (x2) | Power outlets which remain powered on during an EMO event. |
8 | AC RCU power outlet | Internal AC power outlet reserved for sending power to the AC/DC power supply for the RCU. |
9 | AC fan panel power outlet | Internal AC power outlet reserved for sending power to the AC/DC power supply for the fan panels. |
10 | Protective earth terminal | M6 screw protective earth terminal directly connected to the input connector Earth GND terminal. This protective earth terminal should be connected to the main GND bus bar of the ATE Core Configurations Generation 2 system. |
Part Number | Description |
---|---|
788846-03 | Power Cord, AC, IEC 60309 Blue, 6H, 16A, P+N+E Connector to CEE7/7 3P, 3.0 m |
788847-03 | Power Cord, AC, IEC 60309 Blue, 6H, 16A, P+N+E Connector to NEMA 5-20P, 3.0 m |
788848-01 | Power Cord, AC, IEC 60309 Blue, 6H, 16A, P+N+E Connector to IEC C20, 12" |
Part Number | 788849-01[1]1 The Mennekes part number for this part is ME 320C6-180. |
---|---|
Description | IEC 60309 Blue, 6H, 16/20A, P+N+E Pin and Sleeve Connector |
- Double pole fuses feeding RCU power, C13 AUX power, and fan power
- Input double pole fuses
Callout | Fuse | Specification | Value |
---|---|---|---|
1 | Double pole fuses, RCU power, C13 AUX power, and fan power | Current rating | 6.3 A |
Minimum voltage range | 240 V | ||
Voltage rating | 440 V | ||
Size | 3AB, 6.3 mm × 32 mm | ||
Fuse type | Time-lag | ||
Recommended replacement | Littelfuse 35616300029 | ||
2 | Double pole fuses, input | Current rating | 20 A |
Minimum voltage range | 240 V | ||
Voltage rating | 600 V | ||
Size | 5 mm × 20 mm | ||
Fuse type | Time-lag | ||
Recommended replacement | Bel Fuse 0ADKC9200-BE |
RMX-10140-24S2 Single-Phase PEP
Figure Callout | Name | Description |
---|---|---|
1 | Functional earth terminal | Optional functional earth terminal for connection to facility GND. It is not required to connect to the functional earth terminal since the input power connector is industrial-rated with a reliable GND connection. |
2 | Input power connector | IEC 60309, P+N+E, 30 A, 250 V, 6H inlet connector. |
3 | Main disconnect branch breaker | 30 A rated branch input breaker. |
4 | Outlet branch breaker | Double-pole, 20 A branch-rated
breaker which supplies power to the PDU1 C19 outlet, RCU power
outlet, fan power outlet, UPS interface, and AUX power C13
outlets. Notice Per 61010-1 requirements, any power that exits the
rack frame must be protected by a 20
A branch-rated breaker. Ensure that external power is
only supplied from the RMX-10151 Single-Phase PDU connected to the
PDU1 C19 outlet in the primary rack. |
5 | UPS loopbacks with functional earth terminal | Optional UPS connection to provide backup power to the RCU and equipment in the rack. |
6 | PDU2 C19 outlet | Distributes rack power through connection to RMX-10151 Single-Phase PDU or direct connection to high-power equipment. |
7 | PDU1 C19 outlet | Distributes rack power through connection to RMX-10151 Single-Phase PDU. PDU1 power can be routed outside of the rack frame. |
8 | C13 AUX outlets (x2) | Power outlets which remain powered on during an EMO event. |
9 | Protective earth terminal | M6 screw protective earth terminal directly connected to the input connector Earth GND terminal. This protective earth terminal should be connected to the main GND bus bar of the ATE Core Configurations Generation 2 system. |
10 | AC fan panel power outlet | Internal AC power outlet reserved for sending power to the AC/DC power supply for the fan panels. |
11 | AC RCU power outlet | Internal AC power outlet reserved for sending power to the AC/DC power supply for the RCU. |
12 | Low-voltage digital communication ports | Ports used for digital communication to and from the RCU and auxiliary equipment. |
Part Number | Description |
---|---|
789895-01 | Power Cord, AC, IEC 60309 Blue, 6H, 24A, P+N+E Connector to IEC 60309 Blue, 6H, 24A, P+N+E Connector, 2.5 m |
789896-2R5 | Power Cord, AC, IEC 60309 Blue, 6H, 24A, P+N+E Connector to NEMA L6-30, 2.5 m |
Part Number | 789897-01[2]2 The Mennekes part number for this part is ME 330C6-122. |
---|---|
Description | IEC 60309 Blue, 6H, 30/32A, P+N+E Pin and Sleeve Connector |
- Double pole fuses feeding RCU power, C13 AUX power, and fan power
- Input double pole fuses
Callout | Fuse | Specification | Value |
---|---|---|---|
1 | Double pole fuses, RCU power, C13 AUX power, and fan power | Current rating | 6.3 A |
Minimum voltage range | 240 V | ||
Voltage rating | 440 V | ||
Size | 3AB, 6.3 mm × 32 mm | ||
Fuse type | Time-lag | ||
Recommended replacement | Littelfuse 35616300029 | ||
2 | Double pole fuses, input[3]3 Fuses F2 and F4 fuse the C19 outlet labeled PDU 2. Fuses F1 and F3 fuse all other outlets. | Current rating | 20 A |
Minimum voltage range | 240 V | ||
Voltage rating | 600 V | ||
Size | 5 mm × 20 mm | ||
Fuse type | Time-lag | ||
Recommended replacement | Bel Fuse 0ADKC9200-BE |
Single-Phase RMX-10140 PEP Power Requirements
Power Specification | RMX-10140-16S2 | RMX-10140-24S2 | |
---|---|---|---|
Input power rating | Connector | IEC 60309 20A | IEC 60309 30A |
Overvoltage category | II | II | |
Branch circuit rating | 20 A | 30 A | |
Voltage rating | 100 V AC to 240 V AC | 100 V AC to 240 V AC | |
Frequency | 50/60 Hz | 50/60 Hz | |
Current rating | 16 A | 24 A | |
Primary power outputs | Connector | C19 (x1) | C19 (x2) |
Voltage | Same as input | Same as input | |
Current rating | 16 A per output | 16 A per output | |
Frequency | Same as input | Same as input | |
EMO status | Disabled during EMO | Disabled during EMO | |
AUX power outputs | Connector | C13 (x2) | C13 (x2) |
Voltage | Same as input | Same as input | |
Current rating | 2.5 A maximum | 2.5 A maximum | |
Frequency | Same as input | Same as input | |
EMO status | On during EMO | On during EMO | |
Fan power output | Connector | Molex-style, 2-pin | Molex-style, 2-pin |
Voltage | Same as input | Same as input | |
Power rating | 250 W | 250 W | |
Frequency | Same as input | Same as input | |
Current rating | Double pole fused at 6.3 A | Double pole fused at 6.3 A | |
EMO status | Disabled during EMO | Disabled during EMO | |
Rack control unit (RCU) power output | Connector | Molex-style, 3-pin | Molex-style, 3-pin |
Voltage | Same as input | Same as input | |
Power rating | 150 W | 150 W | |
Frequency | Same as input | Same as input | |
Current rating | Double pole fused at 6.3 A | Double pole fused at 6.3 A | |
EMO status | On during EMO | On during EMO |
Related Information
- Uninterruptable Power Supply (UPS)
You can use the UPS to power critical components in your system during power loss, brownouts, and during normal operation as well. It acts as a battery power supply after a power outage or significant brownout.
- Emergency Shutdown (EMO)
When a test system encounters a serious issue or an emergency is taking place in the facility, operators need the ability to quickly and cleanly power off the test system. EMO mechanisms are included on ATE Core Configurations Generation 2 systems to simplify connectivity and inhibit power switching.
- Connecting Power to Connectorized PEPs
- Replacing a Connectorized Power Entry Panel
- Replacing a Fuse in an RMX-10140-16S2 or RMX-10140-24S2 Power Entry Panel
- Grounding
Protective earthing is provided by the appliance inlet. Grounding terminals can be used for a supplemental or functional ground strap.