Synchronizing Analog Input C Series Modules with NI-DAQmx in LabVIEW NXG

Publish Date: May 24, 2017 | 0 Ratings | 0.00 out of 5 | Print | Submit your review

Overview

CompactDAQ controllers and chassis offer support for a wide variety of C Series I/O modules with diverse measurement types such as acceleration, temperature, and strain. When applications require tight synchronization between measurements, the CompactDAQ hardware in conjunction with the NI-DAQmx API allows flexible configuration options to achieve the desired time correlation across multiple C Series I/O modules. This document highlights some of the diverse options available to achieve synchronization between C Series I/O modules using LabVIEW NXG.

Note: This article focuses in LabVIEW NXG only. If you are using LabVIEW, refer to Synchronizing Analog Input C Series Modules with NI-DAQmx for LabVIEW.

Table of Contents

  1. C Series Analog Input Modules
  2. Start Trigger Synchronization
  3. Sample Clock Synchronization
  4. Multidevice Task
  5. Multirate Synchronization
  6. MultiChassis Tasks
  7. Conclusion
  8. Additional Resources

1. C Series Analog Input Modules

C Series Analog Input Modules can be categorized into four groups based on their synchronization: Reference Clocked*, Delta Sigma, Slow Sampled, and Successive Approximation Register (SAR).

Reference Clocked modules* convert using an internal onboard clock. This onboard clock is disciplined using a phase lock loop to another internal clock or can be disciplined to clocks external to the module. Delta Sigma Modules, such as DSA, use a 24-bit ADC and convert using a clock internal to the module. Slow Sampled Modules use a 24-bit ADC and convert using an external clock that originates from the CompactDAQ controller or chassis. Lastly, SAR Modules use a Successive Approximation ADC (12- or 16-bit) and convert using an external clock.

The method of implementing synchronization may depend on the group that the module falls into. A list of module groupings can be found in the Resources section of this tutorial. In this tutorial, synchronization is defined as the steps or techniques used directly or indirectly via the DAQmx driver to start measurements at the same time and to remove drift between subsequent measurements. While the result of these steps increases the alignment, the focus is to prevent drift.  

Note: Reference Clocked modules are not currently supported in LabVIEW NXG. If you have a Referenced Clocked module, use LabVIEW instead and refer to Synchronizing Analog Input C Series Modules with NI-DAQmx in LabVIEW.

 

Back to Top

2. Start Trigger Synchronization

This section outlines different methods to control when acquisition begins across multiple modules. Because the focus is to simply align the start time across multiple tasks, this method is the most rudimentary way to achieve synchronization.

The first method uses a software function that, when executed, starts acquisition as defined by one DAQmx task. When this function executes in each task at relatively the same time, a similar level of synchronization is seen in the start of the data.

When hardware timing is used and no triggers are configured, executing a DAQmx Start Task will initiate the acquisition. This node causes the CompactDAQ Controller and Chassis to send a digital pulse that begins the acquisition. If the DAQmx Start Task nodes of two independent tasks are placed in the same frame of a sequence structure, then the two tasks begin at the same relative time. However, the separation between the exact start times of the two tasks depends on the software time delay between the executions of the DAQmx Start Task nodes and will therefore vary due to the Operating System. This method is seen in figure 1 where the start of two analog input tasks is controlled during runtime with a DAQmx Start Task inside the same frame of a sequence structure.

Figure 1: Start of Each Task Occurs Inside Sequence Structure.

To avoid the delay, a DAQmx Trigger can be used. This method can configure tasks to start upon a hardware trigger rather than by calling a software function. When using this feature to synchronize tasks, one task will be sending the trigger, and the other task will be receiving the trigger. The task receiving the trigger will wait for the trigger sent from the master task to begin acquisition or generation. When the master task starts, a digital trigger is sent from the master task and starts any task configured to start based upon this signal. This method is seen in the Figure 2 where a DAQmx Control Task is called before the task accepting the ai/Start Trigger ensuring that the Master Task reserves the ai /Start Trigger. 

Figure 2: Trigger Configuration to Start Both Tasks.

To understand trigger and timing nomenclature, you must know which timing engine is reserved for a task. CompactDAQ controllers and chassis have three analog input timing engines: ai, te0, and te1. Each concurrently run task is assigned to a different timing engine to control the sample clock and triggers. For example, the ai/StartTrigger is assigned to the ai timing engine. The NI-DAQmx driver automatically assigns each analog input task to a timing engine starting with ai, then te0, and finally te1. It is important to know which task is using which timing engine, so we set tasks receiving the start trigger to use the signal from the same master task’s timing engine. By reserving the master task first, we are assigning this task specifically to the ai timing engine. Now both tasks can be set to use the master task’s start trigger (ai/StartTrigger).

 

Back to Top

3. Sample Clock Synchronization

Using the above technique, tasks are started at the same time by sharing a start trigger. However, this method will not guarantee that the timing of subsequent measurements between the two tasks will not drift away from each other. A sample clock can be shared between both tasks, so that any task that uses the shared clock can take samples at the same time. Therefore, the two tasks will not drift from each other. As discussed earlier, Compact DAQ controllers and chassis have three analog input timing engines, so the order in which the tasks are reserved will determine the timing engines used by each task. Figure 3 below details how to share the sample clock between tasks. 

Figure 3: Sample Clock and Trigger is Shared.

Since each task shares the same sample clock, this technique requires that the two tasks operate at the same sample rate. This method of synchronization will not work for Delta Sigma because they use a clock on the module to acquire their measurements. The following sections (Multidevice Task and Multirate Tasks) will discuss how to synchronize Delta Sigma Modules.

 

Back to Top

4. Multidevice Task

To help simplify synchronization configuration, NI-DAQmx allows multiple Analog Input channels from various modules to be placed in the same task. To place various modules in the same task, specify multiple channels across different modules in the Physical Channel input to the Create Virtual Channel node. Channels from different modules should be included in the same DAQmx Create Channel if they are intended to have the same measurement configuration (voltage range, and units) and the same timing and triggering information.

Figure 4: Using Different Modules in the Same Task.

If the modules are taking different measurements (such as voltage or current), require different measurement ranges, or need to use different measurement units then use multiple instances of the DAQmx Create Virtual Channel node as seen below.

Figure 5: Multiple DAQmx Create Virtual Channel Nodes Used for One Task to Specify Different Measurement Types.

You can mix different types of analog input modules (SAR, Delta Sigma, and Slow Sampled) in the same task and allow the NI-DAQmx Driver to synchronize them for you. With Multidevice Tasks, DAQmx chooses the best possible method to synchronize the modules. An explanation is provided below of different scenarios and how Multidevice Task synchronizes the measurements.

  • Two SAR/Slow Sampled Modules - When two SAR modules, SAR and Slow Sampled modules, or two Slow Sampled Modules are placed in the same hardware timed task, the DAQmx driver shares the same chassis or controller’s sample clock and start trigger between both modules. For the SAR and Slow Sampled Module configuration, the maximum rate that data is returned is not determined by the Slow Sampled Module. The driver will return duplicate samples for the Slow Sampled module to allow you to run the SAR module at the fastest allowable rate.
  • Two Delta Sigma Modules - When two Delta Sigma Modules are placed in the same hardware timed AI task, the DAQmx driver shares the fastest master timebase between all the modules, resets their ADCs based on the same synchronization pulse, shares a start trigger, and adjusts the reset time. The master timebase is the internal 12.8 MHz or 13.1 MHz clock that Delta Sigma Modules use to acquire measurements.
  • Delta Sigma and SAR/Slow Sampled - When a SAR or Slow Sampled Module and a Delta Sigma are placed in the same hardware timed AI task, the DAQmx driver configures the Delta Sigma Module to export its internal sample clock to be used by the SAR or Slow Sampled Module. The internal sample clock is equivalent to the data rate configured for the Delta Sigma Module

    where:

    • fs is the data rate
    • fm is the internal master timebase specified in each modules specification sheet
    • n/a/b are divisors.
  • The driver will return duplicate samples for the Slow Sampled Module, which allows the Delta Sigma to run at a faster rate.

 

Back to Top

5. Multirate Synchronization

When referencing multiple modules in one task, the same sampling rate will apply to all channels. However, some applications may require synchronization at different rates.

  • Two SAR/Slow Sampled Modules – You do not need to do any additional work to synchronize two SAR Modules or Slow Sampled modules acquiring at different rates in a CompactDAQ chassis or controllers besides sharing a Start Trigger. The sample clock each module uses is derived from the same signal. Thus, the measurements will be synchronized if the modules are in the same chassis.
  • Two Delta Sigma Modules - To synchronize two Delta Sigma Modules acquiring at different rates, set the tasks to share a common master timebase, synchronization pulse (sync pulse), and start trigger. The master timebase clock is routed from one module to another in the Figure 6. Note that the NI DAQmx Timing Property node SampleClck.Timebase.Src refers to the same 12.8 MHz or 13.1 MHz signal as the master timebase listed in the Operating Instructions and Specifications/Datasheet. This clock is also known as an oversample clock because there are many ticks of this clock required to produce one sample.

Figure 6: Sharing the Over Sample Clock.

A device that uses a Delta Sigma Module has a free-running ADC. Sharing the master timebase will ensure that measurements are derived from the same clock, but there will be an unknown phase shift due to the exact start of the ADC. The next step is sharing the synchronization pulse. The sync pulse is used to reset the ADC/DAC before it begins acquiring or generating samples. Without this signal to reset the ADC/DAC, measurements taken will not be synchronized. Below are shown the properties that allow the sharing of an oversample clock and a sync pulse.

Figure 7: Sharing Over Sample Clock, Start Trigger and Sync Pulse.

The above configuration routes the synchronization pulse from one task to another depending on which task is running at a faster rate. For multirate configuration, we use the sample clock of the slower running task to trigger the faster running task. The reasoning for this is explained in the example.

One more consideration to study is the reset time required by each module. The reset time is a delay required by a Delta Sigma Modules ADC after it has received the synchronization pulse until it begins acquiring data. Different model Delta Sigma Modules may have different reset times. You need to account for this reset time to ensure each device has gone through the reset sequence and begins to acquire or output samples at the same time. To properly account for potentially different reset times, the reset time required for each module is checked and, if necessary, a delay added to modules with a shorter reset time. Therefore, the sum of the reset time and the delay should be the same for each module.

The time needed to reset the ADC can be found using the SyncPulse.ResetTime property that can be found in the Timing properties from the DAQmx Task properties node. To ensure all ADCs end their reset cycle coincidentally, a comparison is made between both tasks’ reset time. We take the task with the largest Reset Time and subtract the Reset Time of the task with the smallest Reset Time. The result is the time where the one task has begun to acquire data while the other task is still going through its reset cycle. To account for this delay we use another NI-DAQmx property called SyncPulse.ResetDelay. This property allows a delay in the sync pulse that will be sent to each module. As previously stated the reset time is the delay between when the ADC receives a sync pulse and begins to acquire data. To best use this property, you should set this equal to the difference between the module that has the greatest reset time and the reset time of the module. This will shift the synchronization pulse of a module that takes less time to reset thus ensuring that both modules with a slow and fast reset time end their reset sequence at the same time. The code below details how to get the reset time and determine the appropriate reset delay.  

Figure 8: Sync Pulse Reset Time Query and Calculating the Reset Delay.

The NI-DAQmx SyncPulse.ResetDelay property has a maximum input of .013 seconds, which may not be suitable for large differences in the Reset Delay values of differing modules. Note the order of the property node when polling for the SyncPulse.ResetTime on the task receiving the master timebase. The value will change depending on a 13.1 MHz Timebase or 12.8 MHz Timebase. Thus, it is important to call the SyncPulse.ResetTime on this task after the module has been informed of the Master Timebase’s rate.

When searching for the properties SyncPulse.ResetDelay and SyncPulse.ResetTime, you will also encounter SyncPulse.SyncTime and SyncPulse.MinDelaytoStart. Most developers will not use this property but may encounter them due to their similarity in name and proximity in location. SyncPulse.SyncTime is the SynchPulseResetTime plus the value you enter for SyncPulse.ResetDelay. The value of SyncPulse.SyncTime is rounded to the nearest millisecond. SyncPulse.MinDelaytoStart is the time between when the Synchronization Pulse is issued and master task issues the start trigger. This property is equal to SyncPulse.SynchTime unless explicitly set.

Delta Sigma Module and SAR/Slow Sampled Module – To synchronize a Delta Sigma Module and SAR/Slow Sampled Module, share the Delta Sigma Module’s master timebase and sample clock with the SAR/Slow Sampled Module. Since the SAR/Slow Sampled Module cannot acquire at 12.8 MHz or 13.1 MHz the Delta Sigma’s master timebase is shared with the master timebase of the SAR/Slow Sampled Module as depicted in figure 10. The sample clock of a SAR/Slow Sampled Module is typically derived from the CompactDAQ Chassis or Controller’s onboard clock. This method replaces the chassis or controller clock with the 12.8 MHz or 13.1 MHz clock from the Delta Sigma Module. 

Figure 9: Synchronizing a Delta Sigma Module and SAR/Slow Sampled Module.

 

Back to Top

6. MultiChassis Tasks

Some measurement applications require mixed measurements and distributed systems, which might require more than one CompactDAQ chassis or controller. There are three main methods of multichassis synchronization.

Multi Chassis Synchronization Using BNC/SMB Connectors or Digital Modules - One method to achieve synchronization between chassis is to use the two BNC connectors located on the cDAQ-9178, cDAQ-9188, cDAQ-9188XT and cDAQ-9179 chassis or one SMB Connector on the CDAQ-9132, cDAQ-9133, cDAQ-9134, cDAQ-9135, cDAQ-9136, and cDAQ-9137 to import and export timing signals.

Figure 10: cDAQ-9178 with two BNC ports can be used to import or export timing and trigger signals .

The BNC or SMB terminals of different chassis can be connected to route triggers and timing signals. Using the DAQmx driver, signals can be exported from a master task by using the Advance » Export Signal properties from the DAQmx Task properties node. On tasks (in another chassis), the Sample Clock and Start Trigger are configured to use the BNC or SMB terminals to accept signals.

Figure 11: Configuring the BNC Ports on a CompactDAQ Chassis 

Parallel/Correlated Digital IO Modules could also be used to receive or send trigger and timing signals across the chassis. These Digital I/O modules are preferred when there isn’t sufficient BNC or SMB ports on the NI Compact DAQ Controllers and Chassis or the signal bandwidths exceeds that of the BNC or SMB connector (1MHz).

Multichassis Synchronization Using the NI 9469 - The above method to configure timing and trigger signals across the chassis BNC connectors or a Parallel/Correlated Digital IO Modules may work for many applications. However, an alternative method using the NI 9469 is preferable in the following circumstances:

  • Long distance between chassis
  • High bandwidth of the exported signals
  • Complex synchronization topology

The NI 9469 allows simplified signal routing and coding and can offer synchronization to SAR, Slow-Sampled, Delta Sigma, Digital Input and Output, Analog Output modules in differing chassis topologies. The connections between the NI 9469 cards can be configured in Measurement & Automation Explorer (MAX) as shown in the following figure. Please see the related link section at the end of this document for more details on how to configure the NI 9469. 

Figure 12: Configuration of NI 9469 in Measurement & Automation Explorer 

Once the NI 9469 is configured in MAX any module in separate chassis can be added to the same task to greatly simplify the code required for synchronization. The following figure shows how this method of multichassis synchronization.

Figure 13: Multichassis Synchronization Code with NI 9469 Configured in MAX 

The background process for how the modules are synchronized in different chassis is like the stated methods in the Multirate Tasks and Multidevice Tasks Sections. The limitation for which modules in multiple chassis can be synchronized automatically using this approach exists and is documented.

 

Back to Top

7. Conclusion

Throughout this tutorial several synchronization options have been demonstrated. Initially, tasks were started with software timed commands. The level of synchronization can then be improved by sharing a hardware trigger between tasks. Drift between the tasks is prevented by sharing a sample clock from one task to another. When synchronizing at the same rate, programming can be simplified by referring to several modules within the same task. If different rates are required, special considerations depend on what type of module is being used. Finally, in a multiple chassis scenario, options include routing the timing and trigger manually or a more automated process involving the NI 9469. The options outlined above represent an overview of several different ways to accomplish synchronization with LabVIEW NXG and DAQmx using the C Series platform, applicable for the timing requirements in many application areas.

 

Back to Top

8. Additional Resources

Note: Reference Clocked modules and Time Aware CompactDAQ Chassis are not currently supported in LabVIEW NXG. If you have a Referenced Clocked module or a Time Aware CompactDAQ Chassis, use LabVIEW instead and refer to Synchronizing Analog Input C Series Modules with NI-DAQmx in LabVIEW.

Back to Top