MAX 15.0 and NI System Configuration 15.0 Known Issues

Publish Date: Oct 07, 2016 | 0 Ratings | 0.00 out of 5 | Print

This document contains the MAX 15.x and System Configuration 15.x known issues that were discovered before and since the release NI System Configuration 15.0 and 15.3. Not every issue known to NI will appear on this list; it is intended to only show the severe and common issues.

Known Issues by Date

The following items are known issues in MAX 15.x and NI System Configuration 15.x KIL sorted by Date.

113710 Import/Export wizards may fail to report errors
91473 MAX behaves incorrectly with a disconnect ENET device in the system
217233 Exporting LabVIEW RT target configuration without expanding Remote Systems Devices and Interfaces returns incorrect information
225580 DHCP address not assigned if target is not immediately restarted after Network Settings are saved
227480 MAX provides no warning when the same static IP address is used on multiple targets
281382 Find (Systems) VI may hang if executed repeatedly on a Real-Time target
294730 Cannot prevent a Real-Time target from being rebooted by users that do not have reboot permissions
299006 Duplicate entries of LabVIEW software versions may appear in MAX
375447 VxWorks targets crash if Gateway IP is not specified in ni-rt.ini
381557 Deleted cDAQ appears in NI MAX even if it is physically removed from the network
383091 Installation has a long timeout when the target goes offline during deletion of files
399803 The Initialize Session VI fails if the username is set to Admin unless System Configuration Remote Support is installed on the target.
400589 On NI Linux Real-Time targets, you cannot read the IP settings immediately after setting them using NI System Configuration API
408978 IPAddrMode values for myRIO are different for System Session and System Hardware property nodes
429277 After changing network adapter properties using the Hardware Property node, the System Configuration session is no longer valid.
429278 Closing a System Configuration session does not completely clear session information from memory.
474723 Setting or reading DST Enabled using the NI System Configuration API on a Linux RT target results in error -2147220364
531487 GPIB ENET devices in MAX fail to open a configuration interface in the Microsoft Edge web browser
534133 Remote System Discovery Troubleshooting Wizard does not detect foreign LabVIEW and LabVIEW module versions
573183 NI System Configuration returns error -2147220361 (Password supplied for the operation is invalid) about 0.2% of the time
554232 Cannot format or install NI Linux-RT targets that has been in safe mode for several days
552242 Set System Image VI does not apply NI-Auth settings when self-imaging
554012 [Mac] NI I/O Trace is not included in Mac NI System Configuration Installer
515183 Reading from a System Configuration “System Status” Property node does not return new data from the target
571470 Web Interface page is not refreshed properly after changing the time setting in MAX
565772 Cannot launch "Reset Configuration Data" utility from MAX with .NET 4.5.2 on Windows 7 x64 Pre-SP1



ID Known Issue
113710

Return
Import/Export wizards may fail to report errors
Under certain situations, Import/Export wizards may display only an error code, rather than a descriptive message. In other cases, these wizards could fail to report an error even if failure did occur.

Workaround: N/A

Reported Version: 4.5    Resolved Version: N/A    Added: 08/03/2009
91473

Return
MAX behaves incorrectly with a disconnect ENET device in the system
ENET Serial or GPIB devices added in MAX are treated as static resources. When the devices are off, MAX still attempts to connect to them. This can cause a timeout if you have a high port count.

Workaround: Delete the ENET devices from MAX.

Reported Version: 4.2    Resolved Version: N/A    Added: 08/03/2009
217233

Return
Exporting LabVIEW RT target configuration without expanding Remote Systems Devices and Interfaces returns incorrect information
If you try to export the configuration of a LabVIEW Real-Time target without expanding Remote Systems Devices and Interfaces on that target, certain items will show up incorrectly in the Export Wizard.

Workaround: Expand Devices and Interfaces on the LabVIEW RT target before trying to export its configuration.

Reported Version: 4.6    Resolved Version: N/A    Added: 08/02/2010
225580

Return
DHCP address not assigned if target is not immediately restarted after Network Settings are saved
If you change the DHCP settings of a Real-Time target running VxWorks, such as a cRIO target, and then save but do not immediately restart the target, the DHCP settings will not persist.

Workaround: Restart immediately after saving.

Reported Version: 4.7    Resolved Version: N/A    Added: 08/02/2010
227480

Return
MAX provides no warning when the same static IP address is used on multiple targets
MAX allows you to use the same static IP address on multiple LabVIEW Real-Time targets without providing any warning or error.

Workaround: N/A

Reported Version: 4.7    Resolved Version: N/A    Added: 08/02/2010
281382

Return
Find (Systems) VI may hang if executed repeatedly on a Real-Time target
Find (Systems) VI may hang if it is executed repeatedly inside a loop on a Real-Time target.

Workaround: N/A

Reported Version: 1.2    Resolved Version: N/A    Added: 04/27/2011
294730

Return
Cannot prevent a Real-Time target from being rebooted by users that do not have reboot permissions
Users that do not have reboot permissions under the Web-Based Security Configuration of a Real-Time target are still able to reboot that target.

Workaround: N/A

Reported Version: 5.0    Resolved Version: N/A    Added: 08/08/2011
299006

Return
Duplicate entries of LabVIEW software versions may appear in MAX
Certain upgrade scenarios can cause multiple entries of the same LabVIEW software version to show up under the Software tree in MAX each time the Software tree is refreshed.

Workaround: N/A

Reported Version: 5.0    Resolved Version: N/A    Added: 08/08/2011
375447

Return
VxWorks targets crash if Gateway IP is not specified in ni-rt.ini

Workaround: Add the Gateway entry manually or do a reformat without saving network settings.

Reported Version: 5.5    Resolved Version: N/A    Added: 09/06/2013
381557

Return
Deleted cDAQ appears in NI MAX even if it is physically removed from the network

Workaround: N/A

Reported Version: 5.5    Resolved Version: N/A    Added: 09/06/2013
383091

Return
Installation has a long timeout when the target goes offline during deletion of files
When trying to process an uninstallation request, multiple file deletions are requested if components get uninstalled. If the target goes offline during that time, it can result in a long wait.

Workaround: N/A

Reported Version: 5.5    Resolved Version: N/A    Added: 09/06/2013
399803

Return
The Initialize Session VI fails if the username is set to Admin unless System Configuration Remote Support is installed on the target.

Workaround: Leave the username blank.

Reported Version: 5.4    Resolved Version: N/A    Added: 09/06/2013
400589

Return
On NI Linux Real-Time targets, you cannot read the IP settings immediately after setting them using NI System Configuration API
On NI Linux Real-Time targets, IP settings modified using the NI System Configuration API cannot immediately be read.

Workaround: Wait a few seconds after modifying the IP settings to read the values.

Reported Version: 5.5    Resolved Version: N/A    Added: 09/06/2013
408978

Return
IPAddrMode values for myRIO are different for System Session and System Hardware property nodes
When reading the IPAddrMode property with the System Configuration API, the System Session property node returns a different value than the System Hardware property node.

Workaround: N/A

Reported Version: 5.5    Resolved Version: N/A    Added: 09/06/2013
429277

Return
After changing network adapter properties using the Hardware Property node, the System Configuration session is no longer valid.

Workaround: Update the network adapter properties using NI Measurement & Automation Explorer.

Reported Version: 14.0    Resolved Version: N/A    Added: 08/04/2014
429278

Return
Closing a System Configuration session does not completely clear session information from memory.

Workaround: N/A

Reported Version: 14.0    Resolved Version: N/A    Added: 08/04/2014
474723

Return
Setting or reading DST Enabled using the NI System Configuration API on a Linux RT target results in error -2147220364

Workaround: Use NI Measurement & Automation Explorer to set the property.

Reported Version: 5.6    Resolved Version: N/A    Added: 08/04/2014
531487

Return
GPIB ENET devices in MAX fail to open a configuration interface in the Microsoft Edge web browser
When you attempt to configure a GPIB ENET device through the web configuration, you cannot open the browser page by the devices .local hostname.

Workaround: Open the web interface configuration by the devices IP address or use another web browser to open the web interface configuration by .local hostname.

Reported Version: 15.0    Resolved Version: N/A    Added: 08/11/2015
534133

Return
Remote System Discovery Troubleshooting Wizard does not detect foreign LabVIEW and LabVIEW module versions
The Remote System Discovery Troubleshooting Wizard released in MAX 15.0 will not successfully detect foreign LabVIEW installations on a system. The wizard incorrectly reports that no LabVIEW software is installed on the system.

Workaround: There is no workaround for the issue, however the wizard can be advanced to the next page to continue troubleshooting.

Reported Version: 15.0    Resolved Version: N/A    Added: 08/11/2015
573183

Return
NI System Configuration returns error -2147220361 (Password supplied for the operation is invalid) about 0.2% of the time
When using the Install All VI to install software on a NI Real Time target, the Install All VI will return error -2147220361 (Password supplied for the operation is invalid) about 0.2% of the time.

Workaround: Restart the application using the Install All VI

Reported Version: 15.0    Resolved Version: N/A    Added: 5/12/2016
554232

Return
Cannot format or install NI Linux-RT targets that has been in safe mode for a few days
When left in safe-mode for several days, the /var/log/messages directory on an NI Linux-RT target can grow.

Workaround: Contact NI support for Safemode recovery media.

Reported Version: 15.0    Resolved Version: N/A    Added: 5/12/2016
552242

Return
Set System Image VI does not apply NI-Auth settings when self-imaging
When imaging the cRIO-9068 target by running Set Image VI on cRIO, the user settings in the image cannot be applied to the cRIO target.

Workaround: Use a remote system to apply an image or do not use non-default NI-Auth settings.

Reported Version: 15.0    Resolved Version: N/A    Added: 5/12/2016
554012

Return
[Mac] NI I/O Trace is not included in Mac NI System Configuration Installer
NI I/O Trace is not installed by the NI System Configuration installer as on a Windows OS.

Workaround: Install NI-VISA for Mac.

Reported Version: 15.0    Resolved Version: N/A    Added: 5/12/2016
515183

Return
Reading from a System Configuration “System Status” Property node does not return new data from the target
Reading from a “System Status” property node does not pull new data from the target, but rather reads data from the session. The status property is updated when an action in the session (for example, Restart.vi) is responsible for the change in status, but not otherwise.

Workaround: Reopen the session and the System Status property will be updated.

Reported Version: 15.0    Resolved Version: N/A    Added: 5/12/2016
571470

Return
Web Interface page is not refreshed properly after changing the time setting in MAX
After changing the time zone in MAX, refreshing the WIF page cause the page load improperly.

Workaround: N/A

Reported Version: 15.3    Resolved Version: N/A    Added: 5/12/2016
565772

Return
Cannot launch "Reset Configuration Data" utility from MAX with .NET 4.5.2 on Windows 7 x64 Pre-SP1
When .NET 4.5.2 is present on a on Windows 7 x64 Pre-SP1 system, launching Tools >> Reset Configuration Data in MAX fails to reset the configuration data. The application can be manually launched from outside of MAX.

Workaround: Upgrade to System Configuration 16.0 or update to Windows 7 x64 SP1

Reported Version: 15.0    Resolved Version: 16.0    Added: 08/01/2016