Table Of Contents

PXIe-8840 Specifications

Version:
    Last Modified: March 10, 2017

    spd-note-note
    Note  

    Specifications are subject to change without notice.

    spd-note-caution
    Caution  

    Using the PXIe-8840 controller in a manner not described in this user manual can impair the protection the controller provides.

    Features

    PXIe-8840
    CPU Intel® Core™ i5 4400E (2.7 GHz dual-core processor)
    On-die L2 cache 3 MB
    Single-Channel 1600 MHz DDR3L RAM, PC3 12800 4 GB standard, 8 GB maximum
    Hard Drive 250 GB Serial ATA, minimum*
    Ethernet Two 10/100/1000 BaseT ports
    PXI Express 4 Link Configuration x4, x4, x4, x4
    PXI Express 2 Link Configuration x8, x8
    GPIB (IEEE 488 Controller) Yes
    Serial Port (RS-232) Yes (1)
    Parallel Port No
    Hi-Speed USB (2.0) Ports Yes (4)
    SuperSpeed USB (3.0) Ports Yes (2)
    ExpressCard/34 Slot (available on the PXIe-8840 ExpressCard variant only) Yes
    PS/2 Keyboard/Mouse Connector No
    PXI Trigger Bus Input/Output Yes
    Installed Operating System Windows 7 Professional
    * Extended-temperature 24/7 option provides 80 GB minimum SATA solid-state drive.

    Front Panel Dimensions

    The following figure shows the front panel layout and dimensions of the PXIe-8840. Dimensions are in inches (millimeters).

    Figure 1. PXIe-8840 Front Panel Layout and Dimensions

    Electrical

    spd-note-note
    Note  

    Does not include any attached USB devices or ExpressCard.

    Voltage (V) Current (Amps) Typical Current (Amps) Maximum
    +3.3 V 1.03 A 1.65 A
    +5 V 1.33 A 2.48 A
    +12 V 2.87 A 5.16 A
    -12 V 0 A 0 A
    +5 VAux 0.20 A 0.41 A

    Physical

    Board dimensions

    Four-wide 3U PXI Express module

    Slot requirements

    One system slot plus three controller expansion slots

    Compatibility

    Fully compatible with PXI Express Specification 1.0

    Weight

    1.32 kg (2.91 lb) typical

    Environmental

    Maximum altitude

    2,000 m (800 mbar) (at 25 °C ambient)

    Pollution Degree

    2

    Indoor use only.

    Operating Environment

    spd-note-caution
    Caution  

    The operating temperature must not be exceeded, even when used in a chassis with a higher temperature range.

    Ambient temperature range

    5 °C to 50 °C (Tested in accordance with IEC-60068-2-1 and IEC-60068-2-2. Meets MIL-PRF-28800F Class 3 high temperature limit.)

    Extended temperature option

    0 °C to 55 °C (Tested in accordance with IEC-60068-2-1 and IEC-60068-2-2. Meets MIL-PRF-28800F Class 3 low temperature limit and MIL-PRF-28800F Class 2 high temperature limit.)

    Relative humidity range

    10% to 90%, noncondensing (Tested in accordance with IEC-60068-2-56.)

    Storage Environment

    Ambient temperature range

    -40 °C to 65 °C (Tested in accordance with IEC 60068-2-1 and IEC 60068-2-2. Meets MIL-PRF-28800F Class 3 low temperature limit.)

    Extended Temperature Option

    -40 °C to 71 °C (Tested in accordance with IEC 60068-2-1 and IEC 60068-2-2. Meets MIL-PRF-28800F Class 3 limits.)

    Relative humidity range

    5% to 95%, noncondensing (Tested in accordance with IEC 60068-2-56.)

    Shock and Vibration

    Operating shock

    30 g peak, half-sine, 11 ms pulse (Tested in accordance with IEC 60068-2-27. Meets MIL-PRF-28800F Class 2 limits.)

    Random vibration

    Operating

    5 Hz to 500 Hz, 0.3 grms (with solid-state hard drive)

    Nonoperating

    5 Hz to 500 Hz, 2.4 grms (Tested in accordance with IEC 60068-2-64. Nonoperating test profile exceeds the requirements of MIL-PRF-28800F, Class 3.)

    Safety

    This product is designed to meet the requirements of the following standards of safety for information technology equipment:
    • IEC 61010-1, EN 61010-1
    • UL 61010-1, CSA 61010-1
    spd-note-note
    Note  

    For UL and other safety certifications, refer to the product label or the Online Product Certification section.

    Electromagnetic Compatibility

    This product meets the requirements of the following EMC standards for electrical equipment for measurement, control, and laboratory use:

    • EN 61326-1 (IEC 61326-1): Class A emissions; Basic immunity
    • EN 55011 (CISPR 11): Group 1, Class A emissions
    • EN 55022 (CISPR 22): Class A emissions
    • EN 55024 (CISPR 24): Immunity
    • AS/NZS CISPR 11: Group 1, Class A emissions
    • AS/NZS CISPR 22: Class A emissions
    • FCC 47 CFR Part 15B: Class A emissions
    • ICES-001: Class A emissions
    spd-note-note
    Note  

    In the United States (per FCC 47 CFR), Class A equipment is intended for use in commercial, light-industrial, and heavy-industrial locations. In Europe, Canada, Australia and New Zealand (per CISPR 11) Class A equipment is intended for use only in heavy-industrial locations.

    spd-note-note
    Note  

    Group 1 equipment (per CISPR 11) is any industrial, scientific, or medical equipment that does not intentionally generate radio frequency energy for the treatment of material or inspection/analysis purposes.

    spd-note-note
    Note  

    For EMC declarations and certifications, and additional information, refer to the Online Product Certification section.

    CE Compliance

    This product meets the essential requirements of applicable European Directives, as follows:

    • 2014/35/EU; Low-Voltage Directive (safety)
    • 2014/30/EU; Electromagnetic Compatibility Directive (EMC)

    Online Product Certification

    Refer to the product Declaration of Conformity (DoC) for additional regulatory compliance information. To obtain product certifications and the DoC for this product, visit ni.com/certification, search by model number or product line, and click the appropriate link in the Certification column.

    Environmental Management

    NI is committed to designing and manufacturing products in an environmentally responsible manner. NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers.

    For additional environmental information, refer to the Minimize Our Environmental Impact web page at ni.com/environment. This page contains the environmental regulations and directives with which NI complies, as well as other environmental information not included in this document.

    Waste Electrical and Electronic Equipment (WEEE)

    spd-note-weee
    EU Customers  

    At the end of the product life cycle, all NI products must be disposed of according to local laws and regulations. For more information about how to recycle NI products in your region, visit ni.com/environment/weee.

    Battery Replacement and Disposal

    spd-note-battery-directive
    Battery Directive  

    This device contains a long-life coin cell battery. If you need to replace it, use the Return Material Authorization (RMA) process or contact an authorized National Instruments service representative. For more information about compliance with the EU Battery Directive 2006/66/EC about Batteries and Accumulators and Waste Batteries and Accumulators, visit ni.com/environment/batterydirective.

    电子信息产品污染控制管理办法(中国RoHS)

    spd-note-china-rohs
    中国客户  

    National Instruments符合中国电子信息产品中限制使用某些有害物质指令(RoHS)。关于National Instruments中国RoHS合规性信息,请登录 ni.com/environment/rohs_china。(For information about China RoHS compliance, go to ni.com/environment/rohs_china.)

    374236A-01