Table Of Contents

DAQmx Auto-Configure cDAQ Sync Connections (G Dataflow)

Last Modified: August 30, 2018

Detects and configures cDAQ Sync connections between devices.

Stop all NI-DAQmx tasks running on the devices prior to running this node, because any running tasks cause auto-configuration to fail.

spd-note-note
Note  

Auto-configure toggles lines on ports during configuration. Upon completion, all previous configurations are deleted.

connector_pane_image
datatype_icon

dev in

dev in is the name as configured in MAX of the device to which this operation applies. A DAQmx device name constant lists all devices installed in the system.

datatype_icon

error in

error in describes error conditions that occur before this node runs. This input provides standard 'error in' functionality.

datatype_icon

timeout

timeout specifies the time in seconds to wait for the device to respond before timing out. If a timeout occurs, no configuration is changed.

datatype_icon

dev out

dev out is the name of the device the operation applied to.

datatype_icon

error out

error out contains error information. If error in indicates that an error occurred before this node ran, error out contains the same error information. Otherwise, error out describes the error status that this node produces.

datatype_icon

connections configured

connections configured returns the configured port-to-port connections.