Table Of Contents

Start.AnlgMultiEdge.Hysts

Last Modified: February 1, 2019

Specifies an array of hysteresis levels in the units of the measurement or generation. If the corresponding element of Start.AnlgMultiEdge.Slopes is Rising, the trigger does not deassert until the source signal passes below the corresponding element of Start.AnlgMultiEdge.Lvls minus the hysteresis. If Start.AnlgEdge.Slope is Falling, the trigger does not deassert until the source signal passes above Start.AnlgEdge.Lvl plus the hysteresis. Hysteresis is always enabled. Set this property to a non-zero value to use hysteresis. Each element of the array corresponds to a source in Start.AnlgMultiEdge.Srcs and an element in each of the other Analog Multi Edge property arrays, if they are not empty.

Data type: datatype_icon

Long Name: Trigger:Start:Analog Multi Edge:Hystereses

Class: DAQmx Task

Permissions: Read/Write

Where This Property Is Available:

Desktop OS: Windows

FPGA: Not supported

Web Server: Not supported in VIs that run in a web application