Table Of Contents

CO.ConstrainedGenMode

Last Modified: August 16, 2018

Specifies constraints to apply when the counter generates pulses. Constraining the counter reduces the device resources required for counter operation. Constraining the counter can also allow additional analog or counter tasks on the device to run concurrently. For continuous counter tasks, NI-DAQmx consumes no device resources when the counter is constrained. For finite counter tasks, resource use increases with the frequency regardless of the constraint mode. However, fixed frequency constraints significantly reduce resource usage, and fixed duty cycle constraint marginally reduces it.

Data type: datatype_icon

Name Value Description
Unconstrained 14708 Counter has no restrictions on pulse generation.
Fixed High Frequency 14709 Pulse frequency must be above 7.63 Hz and cannot change while the task runs. In this mode, the duty cycle has 8 bits of resolution.
Fixed Low Frequency 14710 Pulse frequency must be below 366.21 Hz and cannot change while the task runs. In this mode, the duty cycle has 16 bits of resolution.
Fixed 50 Percent Duty Cycle 14711 Pulse duty cycle must be 50 percent. The frequency can change while the task runs.

Long Name: Channel:Counter Output:General Properties:More:Advanced:Constrained Generation Mode

Class: DAQmx Task

Permissions: Read/Write

Where This Property Is Available:

Desktop OS: Windows

FPGA: Not supported

Web Server: Not supported in VIs that run in a web application


Recently Viewed Topics