Specifies the states at which signal A and signal B must be while signal Z is high for NI-DAQmx to reset the measurement. If signal Z is never high while signal A and signal B are high, for example, you must choose a phase other than A High B High.

When signal Z transitions to high and how long it stays high varies from encoder to encoder. Refer to the documentation for the encoder to determine the timing of signal Z with respect to signal A and signal B.

Data type: datatype_icon

Name Value Description
A High B High 10040 Reset the measurement when signal A and signal B are high.
A High B Low 10041 Reset the measurement when signal A is high and signal B is low.
A Low B High 10042 Reset the measurement when signal A is low and signal B high.
A Low B Low 10043 Reset the measurement when signal A and signal B are low.

Long Name: Channel:Counter Input:Position:Z Index Phase

Class: DAQmx Task

Permissions: Read/Write

Where This Property Is Available:

Desktop OS: Windows

FPGA: Not supported

Web Server: Not supported in VIs that run in a web application