From 12:00 PM - 4:00 PM CST on Thursday, October 18, ni.com will be undergoing system upgrades that may result in temporary service interruption.

We appreciate your patience as we improve our online experience.

Table Of Contents

Internal Channels for E Series Devices

Last Modified: April 18, 2018

The following table is a list of internal physical channels for all E Series devices. Different E Series devices have different subsets of channels. These channels are typically for self-calibration, and you can sample them as you would a physical channel present on the I/O connector.

Internal Channel Name Description
_aognd_vs_aognd A differential terminal with the positive and negative terminals both connected to the ground reference for analog output.
_aognd_vs_aignd A differential terminal with the positive terminal connected to the ground reference for analog output and the negative terminal connected to the ground reference for analog input.
_ao0_vs_aognd A differential terminal with the positive terminal connected to physical channel ao0 and the negative terminal connected to the ground reference for analog output.
_ao1_vs_aognd A differential terminal with the positive terminal connected to physical channel ao1 and the negative terminal connected to the ground reference for analog output.
_calref_vs_calref A differential terminal with the positive terminal connected to the onboard 5 V reference and the negative terminal connected to the onboard 5 V reference.
_calref_vs_aignd A differential terminal with the positive terminal connected to the onboard 5 V reference and the negative terminal connected to the ground reference for analog input.
_ao0_vs_calref A differential terminal with the positive terminal connected to physical channel ao0 and the negative terminal connected to the onboard 5 V reference.
_ao1_vs_calref A differential terminal with the positive terminal connected to physical channel ao1 and the negative terminal connected to the onboard 5 V reference.
_ao1_vs_ao0 A differential terminal with the positive terminal connected to physical channel ao1 and the negative terminal connected to physical channel ao0.
_boardTempSensor_vs_aignd A differential terminal with the positive terminal connected to the onboard temperature sensor and the negative terminal connected to the ground reference for analog input.
_aignd_vs_aignd A differential terminal with the positive terminal connected to the ground reference for analog input and the negative terminal connected the ground reference for analog input.
_caldac_vs_aignd A differential terminal with the positive terminal connected to the onboard calibration DAC and the negative terminal connected to the ground reference for analog input.
_caldac_vs_calref A differential terminal with the positive terminal connected to the onboard calibration DAC and the negative terminal connected to the onboard 5 V reference.
_PXI_SCXIbackplane_vs_aignd A terminal where a signal being conditioned by a SCXI module is measured across the PXI/SCXI backplane and not the I/O connector. Reading from this channel is valid only on PXI devices inserted in the rightmost PXI slot of a PXI/SCXI combination chassis.