Table Of Contents

Start.AnlgEdge.Hyst

Last Modified: May 21, 2018

Specifies a hysteresis level in the units of the measurement or generation. If Start.AnlgEdge.Slope is Rising, the trigger does not deassert until the source signal passes below Start.AnlgEdge.Lvl minus the hysteresis. If Start.AnlgEdge.Slope is Falling, the trigger does not deassert until the source signal passes above Start.AnlgEdge.Lvl plus the hysteresis. Hysteresis is always enabled. Set this property to a non-zero value to use hysteresis.

Data type: datatype_icon

Long Name: Trigger:Start:Analog Edge:Hysteresis

Class: DAQmx Task

Permissions: Read/Write

Where This Property Is Available:

Desktop OS: Windows

FPGA:

Web Server: Not supported in VIs that run in a web application