Table Of Contents

CtrOutEvent.OutputBehavior

Version:
    Last Modified: May 21, 2018

    Specifies whether the exported Counter Output Event pulses or changes from one state to the other when the counter reaches terminal count.

    Upon reaching terminal count, the counter can issue a pulse. Use CtrOutEvent.Pulse.Polarity to select a high or low pulse.

    Upon reaching terminal count, the output terminal of the counter can change state, or toggle. For example, if the terminal is initially at a low state, it changes to high state and stays at the high state until the next terminal count. The terminal then changes to low state. Use CtrOutEvent.Toggle.IdleState to select the initial state of the terminal.

    When counting up, a counter reaches terminal count when it reaches the maximum value (2^24 - 1 for a 24-bit counter). When counting down, a counter reaches terminal count when it reaches 0.

    Data type: datatype_icon

    Name Value Description
    Pulse 10265 Send a pulse to the terminal.
    Toggle 10307 Toggle the state of the terminal from low to high or from high to low.

    Long Name: Export Signal:CtrOutEvent.OutputBehavior

    Class: DAQmx Task

    Permissions: Read/Write

    Where This Property Is Available:

    Desktop OS: Windows

    FPGA:

    Web Server: Not supported in VIs that run in a web application


    Recently Viewed Topics