Table Of Contents

DAQmx Tristate Output Terminal (G Dataflow)

Version:
    Last Modified: February 6, 2017

    Sets a terminal to high-impedance state.

    If you connect an external signal to a terminal on the I/O connector, the terminal must be in high-impedance state. Otherwise, the device could double-drive the terminal and damage the hardware. If you use this node on a terminal in an active route, the node fails and returns an error.

    DAQmx Reset Device sets all terminals on the I/O connector to high-impedance state, but aborts any running tasks associated with the device.

    connector_pane_image
    datatype_icon

    output terminal

    output terminal specifies the terminal on the I/O connector to set to high-impedance state. A DAQmx terminal constant lists all available terminals on installed devices. You also can specify an output terminal by using a string that contains a terminal name.

    datatype_icon

    error in

    error in describes error conditions that occur before this node runs. This input provides standard error in functionality.

    datatype_icon

    error out

    error out contains error information. This output provides standard error out functionality.

    Where This Node Can Run:

    Desktop OS: Windows

    FPGA: LabVIEW NXG does not support FPGA devices