Table Of Contents

DAQmx Setup SCXI Calibration (1124) (G Dataflow)

Version:
    Last Modified: February 6, 2017

    Writes the specified binary value to the DAC on the specified physical channel at the specified range.

    spd-note-note
    Note  

    Specify at least two calibration points for each physical channel and range you calibrate. Use 0 and 4095 for voltage calibration ranges. Use 255 and 4095 for current calibration ranges.

    connector_pane_image
    datatype_icon

    calHandle in

    calHandle in is a reference to the calibration session that you created using the DAQmx Initialize External Calibration node.

    datatype_icon

    physical channel

    physical channel specifies the physical channel to calibrate.

    datatype_icon

    range

    range specifies the range to calibrate.

    Name Description
    0Volts to 1Volts

    0 V to 1 V.

    0Volts to 5Volts

    0 V to 5 V.

    0Volts to 10Volts

    0 V to 10 V.

    -1Volts to 1Volts

    -1 V to 1 V.

    -5Volts to 5Volts

    -5 V to 5 V.

    -10Volts to 10Volts

    -10 V to 10 V.

    0Amps to 20mAmps

    0 A to 20 mA.

    datatype_icon

    DAC value

    DAC value is the binary number to write to the DAC.

    datatype_icon

    error in

    error in describes error conditions that occur before this node runs. This input provides standard 'error in' functionality.

    datatype_icon

    calHandle out

    calHandle out is a reference to the calibration session. Wire this output to other external calibration nodes.

    datatype_icon

    error out

    error out contains error information. If error in indicates that an error occurred before this node ran, error out contains the same error information. Otherwise, error out describes the error status that this node produces.

    Where This Node Can Run:

    Desktop OS: Windows

    FPGA: LabVIEW NXG does not support FPGA devices