    Configures the task to stop the acquisition when the device acquires all pretrigger samples, detects a rising or falling edge of a digital signal, and acquires all posttrigger samples.

    connector_pane_image
    datatype_icon

    task in

    task in is the name of the task that the operation applies.

    datatype_icon

    source

    source specifies the name of a terminal where there is a digital signal to use as the source of the trigger.

    datatype_icon

    edge

    edge specifies on which edge of the digital signal the Reference Trigger occurs.

    Name Description
    Falling

    Trigger on a falling edge of the digital signal.

    Rising

    Trigger on a rising edge of the digital signal.

    datatype_icon

    error in

    error in describes error conditions that occur before this node runs. This input provides standard 'error in' functionality.

    datatype_icon

    pretrigger samples per channel

    pretrigger samples per channel specifies the minimum number of samples to acquire per channel before recognizing the Reference Trigger. The number of post-trigger samples per channel is equal to number of samples per channel in the DAQmx Timing node minus pretrigger samples per channel.

    datatype_icon

    task out

    task out is a reference to the task after this node runs.

    datatype_icon

    error out

    error out contains error information. If error in indicates that an error occurred before this node ran, error out contains the same error information. Otherwise, error out describes the error status that this node produces.