Table Of Contents

DAQmx Create Virtual Channel (Counter Input » Count Edges) (G Dataflow)

Version:
    Last Modified: February 6, 2017

    Creates a channel to count the number of rising or falling edges of a digital signal. With the exception of devices that support multi-counter tasks, you can create only one counter input channel at a time with this node, because a task can contain only one counter input channel. To read from multiple counters simultaneously, use a separate task for each counter. Connect the input signal to the default input terminal of the counter, unless you select a different input terminal.

    connector_pane_image
    datatype_icon

    task in

    task in specifies the task to which to add the virtual channels this node creates. If you do not specify a task, NI-DAQmx creates a task for you, and adds the virtual channels this node creates to that task.

    datatype_icon

    counter

    counter specifies the name of the counter to use to create the virtual channel. The DAQmx physical channel constant lists all physical channels, including counters, for devices installed in the system.

    datatype_icon

    name to assign

    name to assign specifies a name to assign to the virtual channel this node creates. If you do not wire a value to this input, NI-DAQmx uses the physical channel name as the virtual channel name.

    If you use this input to provide your own names for the virtual channels, you must use the names when you refer to these channels in other NI-DAQmx nodes, such as the source input of the DAQmx Trigger node.

    If you create multiple virtual channels with one DAQmx Create Virtual Channel node, you can specify a comma-separated list of names to assign to the virtual channels. If you provide fewer names than the number of virtual channels you create, NI-DAQmx automatically assigns names to the virtual channels.

    datatype_icon

    error in

    error in describes error conditions that occur before this node runs. This input provides standard 'error in' functionality.

    datatype_icon

    initial count

    initial count is the value from which to start counting.

    datatype_icon

    count direction

    count direction specifies whether to increment or decrement the counter on each edge.

    Name Description
    Count Down

    Decrement counter.

    Count Up

    Increment counter.

    Externally Controlled

    The state of a digital line controls the count direction. Each counter has a default count direction terminal.

    datatype_icon

    edge

    edge specifies on which edges of the input signal to increment or decrement the count.

    Name Description
    Falling

    Count falling edges.

    Rising

    Count rising edges.

    datatype_icon

    task out

    task out is a reference to the task after this node runs. The task contains any newly created virtual channels. If you did not wire a value to task in, NI-DAQmx automatically creates the task this output refers to.

    datatype_icon

    error out

    error out contains error information. If error in indicates that an error occurred before this node ran, error out contains the same error information. Otherwise, error out describes the error status that this node produces.